2015-01-26 09:46:25 | |
| ****REVIEW IN PROGRESS... |
| |
| 1-PROVIDE COPY OF IMPACT FEES PAID RECEIPT. PLANS |
| SUBMITTED HAVE THE PALM BEACH COUNTY IMPACT FEES STAMP, |
| BUT COPY OF PAID RECEIPT WAS NOT SUBMITTED. |
| |
| 2- |
| |
| ***REVIEW IN PROGRESS... |
| |
| 10- TYPICAL WALL SECTION 4/A-2.0: PROVIDE |
| SPECIFICATIONS SHOWING COMPLIANCE WITH THE CLEARANCE |
| FOR TERMITE INSPECTION AS REQUIRED BY SEC. R704 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 11- PROVIDE MANUFACTURER SPECS FOR THE WINDOWS THAT |
| SHOW THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE |
| ENERGY CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONCRETE BLOCK WALL SHOWING COMPLIANCE WITH THE |
| INSULATION R VALUE SPECIFIED ON THE ENERGY CALCULATIONS |
| ON ITEM #9. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| 13- ENERGY CALCULATIONS SUBMITTED: |
| A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| B) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5. SEE |
| PLANS AND PRODUCT APPROVAL AND REVISE AS REQUIRED. SEC. |
| 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| C) COORDIANTE INFORMATION WITH THE EQUIPMENT SIZING |
| CALCULATIONS. SEE MECHANICAL REVIEW COMMENTS. SEC. |
| 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| D) PROVIDE COMPLETE INFORMATION ON TOP OF FORM: OWNER, |
| BUILDER, PERMIT OFFICE AND JURISDICTION NUMBER. SEC. |
| 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 14- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| EACH BEDROOM. THERE IS ONLY ONE CARBON MONOXIDE ALARM |
| SHOWN ON THE HALLWAY AND IT'S MORE THAN 10 FEET AWAY |
| FROM BEDROOMS 2 AND 5. SEC. R315 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) SINGLE HUNG WINDOWS. NOA 12-0127.16 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. |
| |
| B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. PROVIDE ONLY THE COVER PAGE AND PAGE |
| SHOWING THE SPECIFIED CONNECTOR OR ARCHITECT TO LIST |
| THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE |
| SPECIFIED CONNECTOR. |
| |
| 16- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT |
| APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| *** PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. |
| |