2014-12-24 09:25:21NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS CAN NOT BE DONE FOR
 WORST CASE SCENARIO. CALCULATIONS NEED TO BE DONE FOR
 THE ACTUAL BUILDING ORIENTATION AS REQUIRED BY SEC.
 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. REVISE AS
 REQUIRED.
  
 2- PROVIDE THE SELECTED EQUIPMENT SENSIBLE AND TOTAL
 COOLING CAPACITIES AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW OBTAINING R9.2 INSULATION ON CONCRETE WALLS AS
 SPECIFIED ON THE EQUIPMENT SIZING CALCULATIONS. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 4- INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS FOR HEATING DON'T MATCH INFORMATION SHOWN
 ON THE ENERGY CALCULATIONS. REVISE AS REQUIRED TO
 MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 5- CLARIFY WHY THE EQUIPMENT SIZING CALCULATIONS ARE
 TAKING AN OCCUPANT LOAD OF 26 OCCUPANTS FOR THIS HOUSE.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 6- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C PLAN AS REQUIRED BY SEC.
 107.2.1 OF CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ANY REVISED DRAWING.
  