Plan Review Notes
Plan Review Notes For Permit 14120044
Permit Number 14120044
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-23 11:39:23NEW SINGLE FAMILY (R3) BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $180,000. THE PERMIT FEE
 BALANCE IS $3,518.02. SEC. 109.3 CITY AMENDMENTS TO
 FBC.
  
 3- DRAWINGS NEED THE ARCHITECT'S ORIGINAL SIGNATURE
 (NOT RUBBER STAMP) AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTE.
  
 4- ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL THIS PROPERTY IS LOCATED IN EXPOSURE
 "C" NOT "B". REVISE BUILDING CODE INFORMATION ON SHEET
 CS-1, WINDOWS AND DOORS DESIGN PRESSURES ON SHEET
 A-3.0, ROOF FRAMING NOTES ON SHEET S-3.0, ETC.
  
 5- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 6- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 7- SPECIFY ON PLANS ATTIC ACCESS. SEC. R807 OF 2010
 FBC-RESIDENTIAL.
  
 8- NEED GUTTERS WITH DOWNSPOUTS AS REQUIRED BY SEC.
 R318.6 OF 2010 FBC-RESIDENTIAL. REVISE ROOF PLAN ON
 SHEET A-2.0 AND DETAIL 4/A-3.1.
  
 9- REVISE DETAIL 6/A-2.0: STRUCTURAL BUCK NEED TO
 PROVIDE FULL SUPPORT TO THE DOOR FRAME AS REQUIRED BY
 SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. DETAIL SHOWN
 DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME.
  
 10- TYPICAL WALL SECTION 4/A-2.0: PROVIDE
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE CLEARANCE
 FOR TERMITE INSPECTION AS REQUIRED BY SEC. R704 OF 2010
 FBC-RESIDENTIAL.
  
 11- PROVIDE MANUFACTURER SPECS FOR THE WINDOWS THAT
 SHOW THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE
 ENERGY CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONCRETE BLOCK WALL SHOWING COMPLIANCE WITH THE
 INSULATION R VALUE SPECIFIED ON THE ENERGY CALCULATIINS
 ON ITEM #9. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 13- ENERGY CALCULATIONIS SUBMITTED:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5. SEE
 PLANS AND REVISE AS REQRUIED. SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 14- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH BEDROOM. THERE IS ONLY ONE CARBON MONOXIDE ALARM
 SHOWN ON THE HALLWAY AND IT'S MORE THAN 10 FEET AWAY
 FROM BEDROOMS 2 AND 5. SEC. R315 OF 2010
 FBC-RESIDENTIAL.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS RERQUIED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. NOA 12-0127.16 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  
 B)
  
  
 -PRECAST LINTELS.
 -STRUCTURAL CONNECTORS
  
  
  
 ***REVIEW IN PROGRESS...


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved