Plan Review Notes For Permit 14120009 |
Permit Number |
14120009 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-01 14:54:36 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) SUBMIT TWO COPIES OF A DIMENSIONED ROOF DIAGRAM OF | | THE STRUCTURE THAT SHOWS THE ROOF SLOPES AND INDICATE | | THE AREA THAT IS BEING RE-ROOFED. FBC 107.2.1 | | | | 2) THE VALUE OF THE WORK IS TOO LOW FOR RE-ROOFING 1100 | | SQUARE FEET OF CONCRETE TILE. FBC 109.3 | | | | 3) SPECIFY THE UNDERLAYMENT SYSTEM THAT WILL BE USED | | AND INDICATE ITS MAXIMUM DESIGN PRESSURE. THIS CAN BE | | DONE BY CIRCLING THE APPROPRIATE ITEMS FROM THOSE | | LISTED ON PAGES 5 - 8 OF PRODUCT APPROVAL FL5259. THE | | STRUCTURE HAS A MEAN ROOF HEIGHT OF 20 FEET AND IS | | LOCATED IN EXPOSURE CATEGORY C WITH A WINDSPEED OF 170 | | MPH VULT. THE ROOF SLOPE IS 4:12. THE REQUIRED UPLIFT | | IS MORE THAN -90 PSF FOR ROOF ZONE 3. FBC 107.2.1 & | | R301.2.1 | | |
|