2014-12-09 11:13:341ST REVIEW: FBC 2010; NEC 2008
  
 NEC 210.52 (B)(1)& (3) - KITCHEN COUNTER TOP
 RECEPTACLES SHALL BE SUPPLIED BY NO FEWER THAN TWO
 20AMP.SMALL APPLIANCE BRANCH CIRCUITS.
 PANEL SCHEDULE SHOWS 15 AMP.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. NEW
 RECEPTACLES AND NEW DINING AREA
 PLAN ELECTRIC NOTE #8 APPLYS AFCI ONLY TO BEDROOMS.
  