2015-01-13 12:29:1901/13/2015
 PROJECT: TANNING SALON
 PERMIT#: 14110915
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) VERIFY EQUIPMENT GROUND FROM THE 80AMP OCPD
 INDICATED IN PANEL ?A? 14,16,18, TO FEED THE CHILLI
 POWER BED VIA PTR 39 BOOST TRANSFORMER IS UNDERSIZED.
 NEC 250.122.
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) REFER TO MANUFACTURER PRODUCT SPECIFICATIONS
 INDICATING THE NRTL LISTING, VOLTAGE AND KW LOAD AND
 INSTALLATION REQUIREMENTS FOR EACH PIECE OF EQUIPMENT.
 NEC 110.3(B)
  
 4) VERIFY GROUNDING OF THE BUCK BOOST TRANSFORMERS.
 PROVIDE A DETAIL INDICATING HOW TO CONNECT THE BUCK
 BOOST TRANSFORMER'S GROUNDING ELECTRODE BACK TO THE
 MAIN GROUNDING ELECTRODE SYSTEM VIA EQUIPMENT GROUND
 SIZED IN ACCORDANCE WITH THE NEC 250.122
  
 5) OUTLETS INDICATED IN THE FIRE RATED TENANT
 SEPARATION WALL SHALL BE SEPARATED BY A MINIMUM OF 24"
 FROM ANY OUTLETS IN THE ADJACENT TENANT SPACE OR BE
 PROTECTED BY A FIRE RATED MATERIAL APPROVED FOR THAT
 USE.
 FBC 713.3.1.2.
  
 6) ONE 15 OR 20AMP GFI RECEPTACLE OUTLET SHALL BE
 INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING
 OF HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME
 LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS. NEC 210.63 SEE
 210.8(A)(3), VERIFY THE REQUIRED OUTLETS ARE EXISTING
 OR INDICATE NEW OUTLETS INCLUDING THE CIRCUIT IN THE
 CORRESPONDING PANELBOARD.
  
 7) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR NETWORK, DATA, AND, COMMUNICATION
 INSTALLATIONS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  