Plan Review Notes
Plan Review Notes For Permit 14110915
Permit Number 14110915
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-16 16:28:4412/16/2014
 PROJECT: TANNING SALON
 PERMIT#: 14110915
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO INDICATE THE SIZE OF THE
 EXISTING FEEDERS TO PANEL A AND PANEL B. NEC 215.5
  
 2) PROVIDE A SITE PLAN THAT INCLUDES THE LOCATION OF
 BAY#2505, THE LOCATION OF THE EXISTING SERVICE AND THE
 LOCATION OF THE NEW SERVICE TO SHOW COMPLIANCE WITH THE
 NEC 230.72 "GROUPING OF DISCONNECTS,"
  
 3) INDICATE THE ROUTING OF THE NEW SERVICE FEEDER TO
 INDICATE COMPLIANCE WITH NEC 230.3 "ONE BUILDING OR
 OTHER STRUCTURE NOT TO BE SUPPLIED THROUGH ANOTHER."
  
 4) PROVIDE REASONING FOR THE NEW SERVICE TO INDICATE
 COMPLIANCE WITH NEC 230.2 " NUMBER OF SERVICES" .
  
 5) PROVIDE A COMPLETE LOAD CALCULATION OF THE
 ELECTRICAL SERVICE INCLUDING THE EXISTING AND NEW
 PANELS INDICATING THE TOTAL CONNECTED LOAD AFTER THE
 ADDITION OF NEW CIRCUITS. BASED ON PART II AND III OF
 THE NEC 220
  
 6) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 7) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 8) PROVIDE MANUFACTURER PRODUCT SPECIFICATIONS
 INDICATING THE NRTL LISTING, VOLTAGE AND KW LOAD FOR
 EACH PEICE OF EQUIPMENT. NEC 110.3(B)
  
 9) REVISE THE PLANS TO CLARIFY GROUNDING OF THE BUCK
 BOOST TRANSFORMERS. PROVIDE A DETAIL INDICATING HOW TO
 CONNECT THE BUCK BOOST TRANSFORMER'S GROUNDING
 ELECTRODE BACK TO THE MAIN GROUNDING ELECTRODE SYSTEM
 VIA EQUIPMENT GROUND SIZED IN ACCORDANCE WITH THE NEC
 250.122
  
 10) REVISE THE FLOOR PLAN TO INDICATE THE LOCATIONS OF
 THE BUCK BOOST TRANSFORMER WHERE REQUIRED. FBC-WPB
 AMENDMENTS 107.3.5
  
 11) REVISE THE PLAN TO INDICATE THE REQUIRED CLEARANCE
 AND DEDICATED WORKING SPACE ABOUT ELECTRICAL EQUIPMENT
 INCLUDING THE SERVICE EQUIPMENT, SERVICE PANELS, BUCK
 BOOST TRANSFORMERS AND DISCONNECTS FOR TANNING
 EQUIPMENT. NEC110.26
  
 12) REVISE THE PLAN TO INDIACTE THE LOCATION OF THE
 LIGHTING CONTACTOR(S) AND PROVIDE ADDITIONAL DETAIL TO
 INDICATE COMPLIANCE WITH FBC-E 505.2 LIGHTING CONTROLS
 (MANDATORY) LIGHTING SYSTEMS SHALL BE PROVIDED WITH
 CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2,
 505.2.3 AND 505.2.4.
  
 13) THE BRANCH CIRCUIT FEEDING THE EXIT AND EMERGENCY
 LIGHTING EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 700.12(F)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  