2014-12-04 13:17:201) SHT. A-3 - DETAIL #4 - THE DOWNSPOUT FOR THE ROOF
 DRAINAGE SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE
 BUILDING WALL PER THE 2010 FLORIDA BUILDING CODE
 SEC.1503.7.
 2) SUBMIT A RISER DIAGRAM FOR THE STORM DRAIN
 COLLECTION SYSTEM. INDICATE ALL PIPE SIZES AND THE
 SQUARE FOOTAGE OF THE ROOF THAT IS DRAINED BY EACH
 INDIVIDUAL ROOF DRAIN.INCLUDE 1/2 OF THE AREA OF THE
 PARAPET WALL TO THE PROJECTED ROOF AREA CALCULATIONS.
 WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3.
 3) SHT.A-7 - ROOF PLAN - THERE IS A NOTE AT ONE OF THE
 ROOF DRAINS ON THE EXISTING ROOF THAT STATES "SEE NOTE
 10." THERE IS NO NOTE 10 ON THIS PGE.CLARIFY.
 4) THE PVC ON THE ROOF SHALL BE PROTECTED FROM UV RAYS
 PER MANUF. RECOMMENDATIONS AND ASTM REQS, FPC 303.2..
 5) SHT.P-1 - INDICATE THE SIZE OF THE DRAIN FROM THE
 NFHB ON THE ROOF.
  