Plan Review Notes For Permit 14110892 |
Permit Number |
14110892 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-16 18:17:18 | PLAN DENIED | | | | 1) PROVIDE A COMPLETE SET OF PLANS SHOWING | | DUCT SIZE AND CFM PER SECTION 107 FBC 2010 | | 2) PROVIDE ENGINEER DETAIL ON CURB TIE DOWN TO ROOF | | AND RTU TIE DOWN TO CURB PER SECTION 301.12 | | WIND RESISTANCE 2010 FBC (M) | | 3) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER | | CONTROLS 2010 FLORIDA ENERGY CODE. | | 4) SUBMIT ENERGY CALCULATIONS WITH THE PLAN | | PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|