| PROJECT: AUTOZONE 1261 |
| PERMIT#: 14110892 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) REVISE RISER DIAGRAM WITH REPECT TO THE FOLLOWING: |
| A) THE SERVICE ENTRANCE CONDUCTOR SET IS INDICATED AS |
| TWO SETS OF 4, 250MCM ON THE LINE SIDE COMING IN AND |
| THE AFTER THE CT'S IS INDICATED AS TWO SETS OF 4, 3/0. |
| THIS IS CONFLICTING. DETERMINE THE ACTUAL METERING |
| MEATHOD AND INDICATE THIS ACCUARATELY ON THE PLAN. |
| |
| 2) INDICATE LOCATION FOR ALL PANELS AND IDENTIFY EACH |
| ON THE FLOOR PLAN. |
| |
| 3) PROVIDE A SIGN CIRCUIT NEC 600.5. INDICATE THE SIGN |
| CIRCUIT ON THE PANEL SCHEDULE AND INDICATE COMPLIANCE |
| WITH THE FBC-E 505.2 |
| |
| 4) INDICATE COMPLIANCE WITH THE FBC-E 505.2. LIGHTING |
| SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN |
| SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. PROVIDE |
| SCHEDULE AND CONTROL DETAIL FOR LIGHTING CONTACTOR(S) |
| |
| 5) IDENTIFY ALL SYMBOLS, AND CIRCUITS ON FLOOR PLAN. |
| ALL SYMBOLS TO COINCIDE WITH SYMBOLS LEGEND AND ALL |
| CIRCUITS TO COINCIDE WITH PANEL SCEDULE(S). |
| |
| 6) PROVIDE ALL PANEL SCHEDULES. |
| |
| 7) A SEPARATE GROUND ROD AS PROPOSED MUST BE CONNECTED |
| TO THE ELECTRICAL GROUNDING ELECTRODE SYSTEM TO AVOID |
| ANY DIFFERENCE OF POTENTIAL. |
| |
| 8) DRINK MACHINE OUTLET TO BE GFI PROTECTED. NEC 422.51 |
| |
| 9) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. NEC 700.12(F) |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| CCTV, NETWORK, DATA, AND, COMMUNICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |