Plan Review Notes
Plan Review Notes For Permit 14110892
Permit Number 14110892
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-15 14:03:1912/15/2014
 PROJECT: AUTOZONE 1261
 PERMIT#: 14110892
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE RISER DIAGRAM WITH REPECT TO THE FOLLOWING:
 A) THE SERVICE ENTRANCE CONDUCTOR SET IS INDICATED AS
 TWO SETS OF 4, 250MCM ON THE LINE SIDE COMING IN AND
 THE AFTER THE CT'S IS INDICATED AS TWO SETS OF 4, 3/0.
 THIS IS CONFLICTING. DETERMINE THE ACTUAL METERING
 MEATHOD AND INDICATE THIS ACCUARATELY ON THE PLAN.
  
 2) INDICATE LOCATION FOR ALL PANELS AND IDENTIFY EACH
 ON THE FLOOR PLAN.
  
 3) PROVIDE A SIGN CIRCUIT NEC 600.5. INDICATE THE SIGN
 CIRCUIT ON THE PANEL SCHEDULE AND INDICATE COMPLIANCE
 WITH THE FBC-E 505.2
  
 4) INDICATE COMPLIANCE WITH THE FBC-E 505.2. LIGHTING
 SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN
 SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. PROVIDE
 SCHEDULE AND CONTROL DETAIL FOR LIGHTING CONTACTOR(S)
  
 5) IDENTIFY ALL SYMBOLS, AND CIRCUITS ON FLOOR PLAN.
 ALL SYMBOLS TO COINCIDE WITH SYMBOLS LEGEND AND ALL
 CIRCUITS TO COINCIDE WITH PANEL SCEDULE(S).
  
 6) PROVIDE ALL PANEL SCHEDULES.
  
 7) A SEPARATE GROUND ROD AS PROPOSED MUST BE CONNECTED
 TO THE ELECTRICAL GROUNDING ELECTRODE SYSTEM TO AVOID
 ANY DIFFERENCE OF POTENTIAL.
  
 8) DRINK MACHINE OUTLET TO BE GFI PROTECTED. NEC 422.51
  
 9) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. NEC 700.12(F)
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  