2015-05-01 14:35:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 14110863
 ADD: 5483 LEEPER DR.
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: (561) 662-1819
 E-MAIL: RKENNEY @AMCBUILD.COM
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 3RD REVIEW
 DATE: FRIDAY MAY 01/2015
 ACTION: DENIED
  
 1-2 COMPLIED.
  
 3) SEMI-COMPLIED. 3) THE TITLE SHEET LIST THE COMMON
 PATH OF TRAVEL OF 28'-11"/ MAX. PROVIDED (50'). PLEASE
 REFER TO SHEET LS.101 THE MEZZANINE LEVEL FROM THE
 FURTHEST POINT ON THE MEZZANINE TO THE BOTTOM OF THE
 STAIRS A MAXIMUM OF 100 FT. NOTE THIS IS IN A STRAIGHT
 LINE, AS THE CROW FLIES. CHIEF LEDUC AS ASKED FOR A
 LAYOUT OF THE MEZZANINE AREA RACKS OR BENS, WITH
 FURNISHINGS THE TRAVEL DISTANCE WILL DIFFENTLY EXCEED
 THE 100 FT REQUIRING A SECOND EXIT. 1015.2.1 TWO EXITS
 OR EXIT ACCESS DOORWAYS.
  
 4) COMPLIED. SOILS REPORTS SUBMITTED.
  
 5) COMPLIED. RESIDENT INSPECTOR FORMS.
  
 6) A) COMPLIED. SHEET S-3 DOES HAVE THE CORRECT WIND
 DESIGN 170 MPH, EXPOSURE C, BLDG. CAT. II, MEAN ROOM
 HEIGHT OF 34 FT. 8 1/4 INCHES, THE WALL PRESSURES IN
 VASD WALL ZONES 4 & 5, ARE GOOD.
  
 6B) PLEASE NOTE THE 2ND SUBMITTAL FROM NUCOR WITH THE
 CORRECT WIND SPEED OF 170 VULT CONSIST OF SHEETS C1, F1
 & FD1. THE 1ST SUBMITTAL HAD 10 PAGES OF NUCOR PLANSFOR
 THE MEZZANINE AND APPROXIMATELY 5/16 OF AN INCH WORTH
 OF STRUCTURAL PLANS FOR THE BUILDING. THESE PLANS ARE
 MISSING FROM THE NEW 170 MPH PACKAGE.
 DID THE GIRT AND PURLIN LOCATION CHANGE OR ARE THE (2)
 PACKAGES TO BE RECONFIGURED INTO ONE PACKAGE? IS
 ANDERSON-MOORE RESPONSIBLE FOR THE RE-ORGANIZEING THIS
 PAPERWORK? FOR THE REMAINDER OF THIS REVIEW I'M GOING
 TO USE THE REMAINDER OF THE 180 MPH FOR GIRT AND PURLIN
 SPACING TO COMPARE PRESSURES AND SPACING FOR CODE
 COMPLIANCE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 6C) NUCOR WALL PRODUCT APPROVAL FLORIDA REPORT FL
 2686-R3 REVERSE CLASSIC PANEL, PLEASE NOTE THERE ARE
 (2) STRENGTH OF PANELS WITHIN THIS REPORT BOTH BEING 26
 GAUGE METAL PANELS. PLEASE IDENTIFY IF THE 50 KSI OR
 THE 80 KSI ARE TO BE INSTALLED ON THIS PROJECT, THE
 PRESURES ARE DIFFERENT FOR THE SAME SPANS. FOR THE
 INTERIOR WALL ZONE 4, FOR (4) OR MORE SPANS @ 4 FT.
 (BASED ON THE 180 MPH GIRT SPACING SHEETP3 OF 05) THE
 REQIURED PRESSURE OF 44.76 VASD WILL WORK ON EITHER
 CHART, BUT IN WALL ZONE 5 THE END ZONE, WITH THE GIRTS
 SPACED 4 FT. O.C. THE REQUIRED PRESSURE OF 55.02
 NEITHER CHART MEETS THE REQUIRED PRESSURES, IN WALL
 ZONE 5 THE GIRTS WILL NEED TO BE CLOSER TOGETHER TO
 ACHIEVE THE REQUIRED PRESSURE OF 55.02 VASD AS ALLOWED
 BY THE PRODUCT LIMITATIONS. THE DESIGN PRESSURES FOR
 THE REDUCED SUPPORT SPACING MAY BE COMPUTED USING
 RATIONAL ANALYSIS PREPARED BY A FLORIDA PROFESSIONAL
 ENGINEER OR BASED ON NUCOR'S LOAD SPAN TABLE.
  
 6D) NUCOR ROOF PANEL PRODUCT APPROVAL FL4891-R-6
 CLASSIC PANEL HAS THE SAME (2) STRENGTH METALS, A 50KSI
 & 80 KSI. PLEASE IDENTIFY WHICH PRODUCT IS GOING TO BE
 INSTALLED ON THIS PROJECT. THE PRODUCT APPROVAL DOES
 INDICATE THE 50 KSI STEEL HAS TO BE DESIGNED BY OTHERS.
 IT WOULD APPEAR IF THIS PRODUCT IS TO BE INSTALLED THE
 ENGINEER OF RECORD WILL NEED TO BE INVOLVED WITH THE
 DESIGN. THE 80 KSI PRODUCT STATES THAT WITH SUPPORTING
 PURLINS WITH SPACING OF 60.187 INCHES O. C. THE
 PRESSURES ARE GOOD FOR 52.5. WITHIN THIS PRODUCT
 APPROVALS THERE ARE NO SPAN TABLES PROVIDED. NUCORS ROF
 SPANS BASED ON THE 180 MPH SHEET P3 OF 05 INDICATES
 SPANS OF 4 FT. NUCORS STRUCTURAL DESIGN PAGGE A2 ROOF
 PRESSURES ARE IN VULT. WHEN CONVERTED OVER TO VASD ROOF
 ZONE PRESSURES OF ZONE # 1 -41.26,
 ZONE # 2 -71.83 & ZONE # 3 -106.23. PLEASE PROVIDE
 DOCUMENTATION THAT THIS PRODUCT WILL BE ABLE TO MEET
 THESE PRESSURES.
  
 6E) NUCOR BUILDING SYSTEMS IS AN ENGINEERED SYSTEM. FOR
 THE FINAL SET OF PERMITTABLE DOCUMENTS ORIGINAL SIGHED
 & SEALED DOCUMENTS ARE REQUIRED BY FLORIDA
 ADMINISTRTIVE CODE. 61G15-23.002(2) FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS. WHEN ELEMENTS OF THE PROJECT ARE
 SHOWN ON AN ENGINEERING DOCUMENT ONLY FOR INFORMATION
 OR CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY NEW
 1-26-93, FORMERLY 21H-30.003.
  
 7A) SEMI-COMPLIED. THE SUBMITTED PRODUCT APPROVALS FOR
 WALL AND ROOF PANELS ARE NOT IDENTIFIED IN THE PRODUCT
 APPROVALS AS TO KSI. THEY ARE NOT IDENTIED BY CIRCLING
 THE PRODUCTS TO BE USED ON THIS PROJECT ON THE NUCOR
 DRAWINGS LABELED C1 OF 1. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 7B) COMPLIED, NUCOR HAS INDICATED THIS CLASSIC ROOF
 PANEL IS NOT ALLOWED TO TAKE THE DOUBLE REDUCTION AS
 ALLOWED BY THE 2010 FBC-B SECTION 2210.5 / AISI SECTION
 D6.2.1A.
  
 8) COMPLIED, SHEET S3 DOES HAVE THE CORRECT WIND DESIGN
 170 MPH, EXPOSURE C, BLDG. CAT. II, MEAN ROOM HEIGHT OF
 34 FT. 8 1/4 INCHES, THE WALL PRESSURES IN VASD WALL
 ZONES 4 & 5, ARE GOOD.
  
 9A) SEMI-COMPLIED. NUCOR WALL & ROOF PRODUCT APPRVALS
 HAVE BEEN REVIEWED BY THE DESIGNER OF RECORD BUT THE
 VARIABLES ARE THERE, UNKNOWN IF THE 50 OR 80 KSI
 PRODUCT WILL BE INSTALLED, PRESSURES MAYOR MAY NOT
 WORK, ROOF SPAN CHART NOT AVAILABLE AS A REFERANCE.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 9B) COMPLIANCE HAS NOT BEEN MET FOR COMPONENTS AND
 CLADDING. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS RUSKIN WALL LOUVER SUBMITTED, NO FL
 APPROVAL COVER SHEET NOR REVIEWED BY THE DESIGNER OF
 RECORD.
 IT WOULD APPEAR THAT NUCOR IS TAKING THE RESPONSIBILITY
 FOR THEIR WALL AND ROOFING PRODUCCT APPROVALS AND THE
 CONTRACTOR ANDERSON-MOORE WILL BE RESPONSIBLE FOR THE
 EXTERIOR DOORS, WINDOWS AND WALL LOUVERS. SINCE SHEET
 S-3 HAS GOOD DESIGNPRESSURES EITHER THE CONTRACTOR OR
 DESIGNER OF RECORD CAN REQUEST IN WRITING FOR THESE
 PRODUCTS TO BE SUBMITTED AS DEFERRED SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) COMPLIED.
  
 12) THE ENERGY CODE TOTAL BUILDING PERFORMANCE:
 12A) 3RD REQUEST PROVIDE DOCUMENTATION OF CODE
 COMPLIANCE. PLEASE PROVIDE DOCUMENTATION FOR THE SHGC
 VALUES TAKEN OF (0.50) UNDER THE TOTAL BUILDING
 PERFORMANCE ENERGY 506.3.1. THE RESPONSE FROM AMC
 STATES THE ACTUAL SHGC VALUE OF THE GLAZING IS 0.90
 WHICH EXCEEDS THE BASELINE. WHAT I'M ASKING YOU FOR IS
 FOR PROOF THAT THESE WINDOWS MEET A SHGC COEFFIENT OF
 0.90. THE CALCULATED ENERGY CALCULATIONN IS TAKING
 CREDIT FOR IT, PROVE IT!
  
 12B-F) COMPLIED.
  
 13) COMPLIED. IMPACT FEES.
 14) PROVISO: ART IN PUBLIC PLACES
  
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]