Plan Review Notes For Permit 14110863 |
Permit Number |
14110863 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-02 05:39:27 | 1) SHT. P2 - NOTE #1 STATES "REFER TO CIVIL DRAWINGS | | FOR CONTINUATION" BUT THERE ARE NO CIVIL DRAWINGS IN | | THE PLAN SET. SUBMIT A SET OF CIVIL DRAWINGS FOR | | REVIEW. 2ND REQUEST. | | 2) INDICATE ON THE PLANS THAT AN APPROVED TYPE BACKFLOW | | PREVENTION DEVICE WILL BE PLACED AT THE METER PER CITY | | ORDINANCE SEC. 90-33 AND THE CITY'S CROSS CONNECTION | | MANUAL.2ND REQUEST | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|