Plan Review Notes For Permit 14110863 |
Permit Number |
14110863 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-03-04 10:31:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THERE IS INSUFFICIENT DOCUMENTATION JUSTIFYING THE | | CHANGE OF THE OCCUPANCY HAZARD FROM ORDINARY TO | | LOW/LIGHT. | | | | A SECOND EXIT REMAINS A REQUIREMENT FROM THE MEZZANINE. | | | | INFORMATION DOCUMENTED ON THE PROPOSED FIRE SPRINKLER | | SYSTEM INDICATES EXTRA HAZARD GROUP 2 AND ORDINARY | | HAZARD GROUP 2 COMMODITY PROTECTION. BASED ON THIS | | INFOMATION A SECOND EXIT FROM THE MEZZANINE REMAINS A | | REQUIREMENT. ADDITIONALLY, RACK FIRE SPRINKLERS MAY BE | | REQUIRED BASED ON THE REVIEW OF THE BELOW ADDITIONAL | | SUBMITTED INFORMATION. | | | | IN SUPPORT OF YOUR PROPOSED OCCUPANCY HAZARD | | CLASSIFICATION CHANGE, PLEASE PROVIDE A DETAILED | | ACCOUNTING AND FLOOR LAYOUT OF THE STORAGE COMMODITY, | | EACH RACK HEIGHT, EACH RACK LOCATION, INCLUDING ISLE | | WIDTHS, AND HOW THE PRODUCTS ARE PACKAGED, PALLETIZED | | AND STORED. |
|