Plan Review Notes
Plan Review Notes For Permit 14110863
Permit Number 14110863
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2015-03-04 10:31:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT DOCUMENTATION JUSTIFYING THE
 CHANGE OF THE OCCUPANCY HAZARD FROM ORDINARY TO
 LOW/LIGHT.
  
 A SECOND EXIT REMAINS A REQUIREMENT FROM THE MEZZANINE.
  
 INFORMATION DOCUMENTED ON THE PROPOSED FIRE SPRINKLER
 SYSTEM INDICATES EXTRA HAZARD GROUP 2 AND ORDINARY
 HAZARD GROUP 2 COMMODITY PROTECTION. BASED ON THIS
 INFOMATION A SECOND EXIT FROM THE MEZZANINE REMAINS A
 REQUIREMENT. ADDITIONALLY, RACK FIRE SPRINKLERS MAY BE
 REQUIRED BASED ON THE REVIEW OF THE BELOW ADDITIONAL
 SUBMITTED INFORMATION.
  
 IN SUPPORT OF YOUR PROPOSED OCCUPANCY HAZARD
 CLASSIFICATION CHANGE, PLEASE PROVIDE A DETAILED
 ACCOUNTING AND FLOOR LAYOUT OF THE STORAGE COMMODITY,
 EACH RACK HEIGHT, EACH RACK LOCATION, INCLUDING ISLE
 WIDTHS, AND HOW THE PRODUCTS ARE PACKAGED, PALLETIZED
 AND STORED.