2015-03-18 15:44:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 14110863
 ADD: 5483 LEEPER DR.
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: (561) 662-1819
 E-MAIL: RKENNEY @AMCBUILD.COM
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW
 DATE: WED. MARCH 18/2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) 2ND REQUEST . ONLY (1) SOILS REPORT WAS SUBMITTED,
 NOTE THIS JOB REQUIRES A RESIDENT INSPECTOR REQUIRING
 (3) SOILS REPORTS SIGNED AND SEALED.
 1ST REVIEW COMMENT. NO SOILS REPORT WAS SUBMITTED,
 PLEASE PROVIDE A REPORT FOR COMPLIANCE WITH: 2010 FBC-B
 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED. ALSO SEE
 1803.6 REPORTING.
  
 5) THE NEW CONSTRUCTION OF A METAL/ STEEL FRAME
 WAREHOUSE WITH WELDS AND BOLTABLE CONNECTIONS. THIS
 JOBSITE QUALIFIES FOR THE RESIDENT INSPECTOR PROGRAM.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION (WELDING AND BOLTABLE
 CONNECTIONS.
  
 5A) THE RESIDENT INSPECTOR FORMS WILL BE E-MAILED TO
 CONTACT [email protected] PLEASE FILE OUT THE
 RESIDENT INSPECTOR FORMS AND RETURN TO W.P.B. BUILDING
 DEPARTMENT CARE OF JIM WITMER.
  
 FORMS RETURNED ARE MISSING THE ;
 5A)(1) CERTIFIED INSPECTION CO. NAME. SHEET # 4
 5B((2) ARCHITECT AND ENGINEER SEAL & SIGNATURE. SHEET #
 5
  
 5B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 5C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 5D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 5E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
  
  
 6) 2ND REVIEW. SHEET S-3 DOES PROVIDE COMPONENTS AND
 CLADDING PRESSURES FOR WALL ZONES 4 & 5 DESIGNED VULT
 FOR 170 MPH/ 3 SECOND GUST, EXPOSURE C. PRESSURES ARE
 GOOD FOR A 35 FT. MEAN ROOF HEIGHT. SHEET A-4.00
 INDICATES A MEAN ROOF HEIGHT OF 38?-11? AND A EAVE
 HEIGHT OF 34?-8?. BY DEFINITION OF MEAN ROOF HEIGHT WE
 USE THE EAVE HEIGHT WHEN THE ROOF ANGLE OF LESS THAN OR
 EQUAL TO 10 DEGRESS (ACTUAL DEGREES OF 9.74). THE MEAN
 ROOF HEIGHT OF 34?-8? SHOULD BE USED. THE DESIGNER OF
 RECORD IS DEFERRING THE COMPONENTS AND CLADDING
 PRESSURES TO THE NUCOR METAL BUILDING ENGINEER .
  
 THE NUCOR BUILDING IS DESIGNED TO VULT TO 180 MPH,
 EXPOSURE C AND A MEAN ROOF HEIGHT OF 30 FT. (FROM
 FLOOR) NOT THE 35 FT. (34?-8?) TAKEN FROM GRADE. THERE
 IS A DIFFERENCE IN WIND SPEED DESIGN AND MEAN ROOF
 HEIGHT. WITH THE MORE STRIKER WIND DESIGN THE
 COMPONENTS AND CLADDING UNDER THE 170 WILL FAIL
 ALLOWING THE BUILDING TO EITHER IMPLODE OR EXPLODE
 DEPENDING ON THE WIND DIRECTION AND SIZE OF THE BREACH,
 THE BUILDING WAS NOT DESIGNED AS A PARTIALLY OPEN
 BUILDING. THERE CAN ONLY BE ONE DESIGNER OF RECORD FOR
 THE BUILDING, WHEN THE ENGINEERING IS DEFERRED THE TWO
 ENGINEERS NEED TO COME TO A CONCLUSION AS TO WHICH
 DESIGN THE BUILDING IS TO BE BUILT.
  
 COMMENTS FROM 1ST REVIEW. SHEET S-3.0 INDICATES DESIGN
 CRITERIA FOR THE METAL STRUCTURAL PORTION OF THIS
 BUILDING, UNDER THE 1ST REVIEW THERE WAS NO DOCUMENTS
 SUBMITTED FOR REVIEW. NOTE THERE IS NO MENTION TO THE
 COMPONENTS AND CLADDING THAT DEALS WITH THE METAL SKIN
 AS TO THEIR DESIGN CRITERIA? WILL THE WHOLE BUILDING BE
 DESIGNED UNDER ASCE 7-10 OR WILL THERE BE OTHER DESIGN
 CRITERIA FOR THE METAL FRAMING AND CLADDING OF THE
 BUILDING. THE PLANS ARE INCOMPLETE; THERE ARE ALSO NO
 MEZZANINE DETAILS, SHEET S-2.0 FOR BOTH THE FOUNDATION
 AND MEZZANINE BOTH REFER TO THE METAL BUILDING
 MANUFACTURER FOR THE ANCHOR BOLT LAYOUT.
  
  
 7) 2ND REQUEST. THE DESIGNER OF RECORD IS DEFERRING THE
 ROOF PRESSURES AND WALL PANEL PRESSURES TO THE NUCOR
 BUILDING ENGINEER. NUCOR PLANS DOES NOT PROVIDE
 COMPONENT & CLADDING PRESSURES FOR ROOF ZONES NOR WALL
 ZONES. THERE STRUCTURAL CALCULATION SHEET A2 DOES SHOW
 VULT PRESSURES ( ASSUMED, CALCULATIONS DOES NOT STATE
 VULT OR VASD ) FOR ZONES 1, 2, & 3, SHEET A4 WALL
 PRESSURES FOR ZONES 4 & 5 AGAIN PRESSURES DO NOT STATE
 IF THEY ARE VULT OR VASD. NOTES ON BOTH SHEETS INDICATE
 AISI 2007 SPECIFICATIONS. IF THE NUCOR DESIGNERS ARE
 GOING FOR THE DOUBLE REDUCTION IN ALLOWABLE PRESSURES,
 THEY WILL NEED TO SHOW COMPLIANCE WITH AISI 100-2007
 D6.2.1A(A-G). INDICATE IF PRESSURES ARE VULT OR VASD
 AND IF THE REDUCTIONS ALLOWED BY AISI 100-2007 WERE
 TAKEN.
  
 WITHIN THE NUCOR PLANS SUBMITTED THERE ARE NO SECTIONS
 CIRCLED SHOWING WHICH APPLICATIONS WILL BE APPLICABLE
 TO THIS JOB.
  
 NOTE THE NUCOR PLANS C1OF 1 LIST VARIOUS FLORIDA STATE
 APPROVALS NONE HAVE BEEN CIRCLED. THERE ALSO WERE NO
 PRODUCT APPROVALS SUBMITTED FOR EITHER THE WALL PANELS
 OR ROOF PANELS.
  
 PLEASE ALSO SEE THE DESIGNER OF RECORDS COMMENTS AS TO
 THE DEFICIENCIES FOUND IN THE NUCOR BUILDING SYSTEM
 PLANS.
  
 COMMENT 1ST REVIEW. SHEET S-3.0 MISSING THE ROOF
 PRESSURES FOR THE COMPONENTS AND CLADDING. PROVIDE THE
 MEAN ROOF HEIGHT THE PRESSURES WILL BE TAKEN AT. ALSO
 TAKE THE PRESSURES UNDER COMPONENTS AND CLADDING FOR 10
 SQ FT. 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 8) SEMI- COMPLIED, THE PRESSURES PROVIDED ARE GOOD FOR
 A 170 VASD / 35 FT MEAN ROOF HEIGHT. WILL NEED TO
 DISCUSS WITH NUCOR TO SEE WHICH OF THE DESIGN
 PARAMETERS WILL BE USED FOR THE WHOLE OF THE BUILDING.
  
 9) UNABLE TO DETERMINE PRESSURES UNTIL THE WIND DESIGN
 CRITERIA IS DETERMINED BETWEEN THE DESIGNER OF RECORD
 AND NUCORS ENGINEER. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) COMPLIED
  
 12) THE ENERGY CODE TOTAL BUILDING PERFORMANCE:
 12A) 2ND REQUEST PROVIDE DOCUMENTATION OF CODE
 COMPLIANCE. PLEASE PROVIDE DOCUMENTATION FOR THE SHGC
 VALUES TAKEN OF (0.50) UNDER THE TOTAL BUILDING
 PERFORMANCE ENERGY 506.3.1.
  
 12B-F) COMPLIED.
  
 13) COMPLIED. IMPACT FEES.
  
 14) NEW COMMENT: ART IN PUBLIC PLACES
  
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  