Plan Review Notes For Permit 14110863
Permit Number 14110863
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-12-01 15:15:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A FIRE SPRINKLER CONCEPTUAL DRAWING WAS NOT SUBMITTED
 AND IS REQUIRED.
  
 A SECOND MEANS OF EGRESS FROM THE MEZZANINE IS
 REQUIRED. THE COMMON PATH OF TRAVEL IS EXCEEDED PER
 TABLE 40.2.5. OF NFPA 101.