Plan Review Notes For Permit 14110863 |
Permit Number |
14110863 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-01 15:15:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | A FIRE SPRINKLER CONCEPTUAL DRAWING WAS NOT SUBMITTED | | AND IS REQUIRED. | | | | A SECOND MEANS OF EGRESS FROM THE MEZZANINE IS | | REQUIRED. THE COMMON PATH OF TRAVEL IS EXCEEDED PER | | TABLE 40.2.5. OF NFPA 101. |
|