2014-12-23 11:08:43 | 12/23/2014 |
| PROJECT: BE GROUP |
| PERMIT#: 14110863 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION |
| |
| 1) REVISE LIGHTING PLANS TO INCLUDE PROVISIONS FOR |
| COMPLIANCE WITH FBC ENERGY 505.2 LIGHTING CONTROLS |
| (MANDATORY). LIGHTING SYSTEMS SHALL BE PROVIDED WITH |
| CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2, |
| 505.2.3 AND 505.2.4. |
| |
| 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| CCTV, NETWORK, DATA, AND, COMMUNICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |