2014-12-08 16:54:00BUILDING PLAN REVIEW
 PERMIT: 14110863
 ADD: 5483 LEEPER DR
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. 08/2014
 ACTION: DENIED
  
 1) TITLE SHEET T.100 UNDER THE HEADING OF PROJECT DATA
 LIST THIS STRUCTURES OCCUPANCY AS A FACTORY INDUSTRIAL
 GROUP F1 MODERATE HAZARD OCCUPANCY.
 THERE SEAMS TO BE A DISCREPANCY WITHIN THE TITLE SHEET,
 SEE THE TOTAL OCCUPANCY LOADS TAKEN THEY ARE EITHER FOR
 BUSINESS OR STORAGE OCCUPANCIES NOT A
 F1 OCCUPANCY. SHEET LS.100 ALSO LIST THE LARGE AREA AS
 A DISTRIBUTION WAREHOUSE NOT A FACTORY INDUSTRIAL
 OCCUPANCY. PLEASE PROVIDE HOW THE AREA BEING USED AS A
 DISTRIBUTION WAREHOUSE IS CONSIDERED A F1 OCCUPANCY?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. FBC-B
 306.2 FACTORY INDUSTRIAL F-1 MODERATE HAZARD AND SEE
 SECTIONS FBC-B 311.2 S1 OCCUPANCIES & 311.3 S-2 LOW
 HAZARD OCCUPANCIES.
  
 2) DEPENDING ON THE CLASSIFICATION OF TYPE OF STORAGE
 OCCUPANCY S1 VERSES S2 FBC-B TABLE 508.4 MAY REQUIRE
 FIRE RATED OCCUPANCY SEPERATION WALLS.
 THE DESIGNER OF RECORD HAS NOT DECLARED HOW THIS
 STRUCTURE WAS DESIGNED SEE FBC-B :
 508.2.5.1 FIRE-RESISTANCE-RATED SEPARATION.
 508.2.5.2 NONFIRE-RESISTANCE-RATED SEPARATION AND
 PROTECTION.
  
 3) THE TITLE SHEET LIST THE COMMON PATH OF TRAVEL OF
 28'-11"/ MAX. PROVIDED (50'). PLEASE REFER TO SHEET
 LS.101 THE MEZZANINE LEVEL FROM THE FURTHEST POINT ON
 THE MEZZANINE TO THE BOTTOM OF THE STAIRS A MAXIMUM OF
 100 FT. MAXIMUM ALLOWABLE FOR A STORAGE OCCUPANCY
 /SPRINKLERED 100 FT. FBC-B 1014.3 EXCEPTION 1 & 2.
  
 4) THIS IS NEW CONSTRUCTION OF A WAREHOUSE, SHEET S-3
 FOUNDATION NOTE # 9 THE DESIGN CRITERIA FOR THE
 FOUNDATIONS ASSUMES A MINIMUM SAFE BEARING VALUE OF
 2,500 PSF. NO SOILS REPORT WAS SUBMITTED, PLEASE
 PROVIDE A REPORT FOR COMPLIANCE WITH: 2010 FBC-B
 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED. ALSO SEE
 1803.6 REPORTING.
  
 5) THE NEW CONSTRUCTION OF A METAL/ STEEL FRAME
 WAREHOUSE WITH WELDS AND BOLTABLE CONNECTIONS. THIS
 JOBSITE QUALIFIES FOR THE RESIDENT INSPECTOR PROGRAM.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION (WELDING AND BOLTABLE
 CONNECTIONS.
  
 5A) THE RESIDENT INSPECTOR FORMS WILL BE E-MAILED TO
 CONTACT [email protected] PLEASE FILE OUT THE
 RESIDENT INSPECTOR FORMS AND RETURN TO W.P.B. BUILDING
 DEPARTMENT CARE OF JIM WITMER.
  
 5B) 110.4 INSPECTION AGENCIES. THE BUILDING OFFICIAL IS
 AUTHORIZED TO ACCEPT REPORTS OF APPROVED INSPECTION
 AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE
 REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY.
  
 5B) 110.5 INSPECTION REQUESTS. IT SHALL BE THE DUTY OF
 THE HOLDER OF THE BUILDING PERMIT OR THEIR DULY
 AUTHORIZED AGENT TO NOTIFY THE BUILDING OFFICIAL WHEN
 WORK IS READY FOR INSPECTION. IT SHALL BE THE DUTY OF
 THE PERMIT HOLDER TO PROVIDE ACCESS TO AND MEANS FOR
 INSPECTIONS OF SUCH WORK THAT ARE REQUIRED
 BY THIS CODE.
  
 5E) SINCE THIS PROJECT WILL REQUIRE A RESIDENT
 INSPECTOR 3 SETS OF PLANS/ PRODUCT APPROVALS WILL BE
 REQUIRED. 110.3.9.
  
 6) SHEET S-3.0 INDICATES DESIGN CRITERIA FOR THE METAL
 STRUCTURAL PORTION OF THIS BUILDING, UNDER THE 1ST
 REVIEW THERE WAS NO DOCUMENTS SUBMITTED FOR REVIEW.
 NOTE THERE IS NO MENTION TO THE COMPONENTS AND CLADDING
 THAT DEALS WITH THE METAL SKIN AS TO THEIR DESIGN
 CRITERIA? WILL THE WHOLE BUILDING BE DESIGNED UNDER
 ASCE 7-10 OR WILL THERE BE OTHER DESIGN CRITERIA FOR
 THE METAL FRAMING AND CLADDING OF THE BUILDING. THE
 PLANS ARE INCOMPLETE, THERE ARE ALSO NO MEZZANINE
 DETAILS, SHEET S-2.0 FOR BOTH THE FOUNDATION AND
 MEZZANINE BOTH REFER TO THE METAL BUILDING MANUFACTURER
 FOR THE ANCHOR BOLT LAYOUT.
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS /BUILDING ENVELOPE MISSING ROOF
 PRESSURES
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 STAIR SYSTEMS
  
 7) SHEET S-3.0 MISSING THE ROOF PRESSURES FOR THE
 COMPONENTS AND CLADDING. PROVIDE THE MEAN ROOF HEIGHT
 THE PRESSURES WILL BE TAKEN AT. ALSO
 TAKE THE PRESSURES UNDER COMPONENTS AND CLADDING FOR 10
 SQ FT. 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 8) SHEET S-3.0 THE WALL PRESSURES FOR BOTH ZONES 4 &
 END ZONE 5 ARE LOW, THE MEAN ROOF HEIGHT TAKEN AT 42
 FT. ALSO NOTE THE CHART PROVIDES RANGES OF SQ. FT.
 (EXAMPLE 21 TO 50 SQ. FT ) FL CHARTS UNDER BOTH ASCE
 7-10 AND 1609 ARE SPECIFIC 10 SQ. FT., 20 SQ. FT., 50
 SQ. FT. IF YOU HAVE AN OPENING LETS SAY AT 30 SQ. FT.
 THAT IS WHERE YOU INTERPOLATE BETWEEN THE 2 PRESSURES.
 IF THE PRESSUES ARE BEING DERIVED FROM SOME OTHER
 SOURCE PLEASE PROVIDE THE SOURCE?
  
 9) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) LIFE SAFETY SHEET LS.101 THE MEZZANINE LIFE SAFETY
 SHOWS THE SCALE AT 3/32 NDS THIS WOULD EXCEED TRAVEL
 DISTANCES, TYPO SCALE ABOVE FOR THE 1ST FLOOR PLAN IS
 3/16 THS OF AN INCH. 107.2.1.3 ADDITIONAL INFORMATION,
 DISCREPANCY IN PLANS.
  
 12) THE ENERGY CODE TOTAL BUILDING PERFORMANCE:
 12A) PLEASE PROVIDE DOCUMENTATION FOR THE SHGC VALUES
 TAKEN OF (0.50) UNDER THE TOTAL BUILDING
 PERFORMANCEENERGY 506.3.1.
  
 12B) WALLS IN ZONES 3 & 4 BOTH INDICATE THEY ARE IN THE
 NE WALL ZONES WHERE THEY ARE IN THE N.W., S.W. & S.E.
 CORRECT VALUES IN REPORT. TOTAL BUILDING
 PERFORMANCEENERGY 506.3.1.
  
 12C) WINDOWS IN THE N. E. & N.W. WALLS BOTH INDICATE A
 9'-0" TALL WINDOW IN THE ENERGY REPORT WHERE AS THE
 PLANS SHEET A-3.00 INDICATE THEY ARE 10'-0" TALL.
 CORRECT THE ENERGY REPORT FOR CALCULATIONS.
  
 12D) IN THE ENERGY REPORT WINDOWS IN WALL ZONES 3 & 4
 ARE WRONG THEY ARE 22 FT. LONG BUT THE WINDOWS ARE ONLY
 9'-2" TALL INTHIS SECTION.
  
 12E) IN THE ENERGY REPORT THE INTERIOR WALLS FOR ZONES
 3 & 4 ARE NOT CONCRETE WALLS SHEET A-1.01 IDENTIFIES AS
 A WALL MARKER TYPE P1 WALL, PLEASE CORRECT.
  
 12F) THE ROOFING INSULATION IS SHOWN IN THE ENERGY
 REPORT AS A MTL BLDG ROOF R-19, UNDER THE MATERIALS
 USED PORTION OF REPORT IT DECLARES A BUILT UP ROOF 3/8
 INCHES, WITH 6 INCHES OF INSULATION TO MAKE A R-30.3
 VALUE.
 NOTE ABOVE THE OFFICE AREA IS A NON-A/C MEZZANINE. WITH
 A 4 INCH CONCRETE DECK SEPARATING THE AIR CONDITIONED
 OFFICE SPACE FROM THE NON- A/C MEZZANINE, SHEET A7.00
 DETAILS 1-3 SHOW 6 INCH INSULATION LAYED ON TOP OF THE
 DROPPED CEILING TILE.CORRECT VALUES.
  
 12G) SHEET A7.00 DETAILS 1-3 SHOW 6 INCH INSULATION
 LAYED ON TOP OF THE DROPPED CEILING TILE. 2010 ENERGY
 502.2.1.2 CEILING INSULATION.
 INSULATION INSTALLED ON A SUSPENDED CEILING WITH
 REMOVABLE CEILING TILES SHALL NOT BE CONSIDERED PART OF
 THE MINIMUM THERMAL RESISTANCE OF THE ROOF INSULATION
 UNLESS THE ROOF/CEILING CAVITY IS SEALED FROM THE
 EXTERIOR ENVIRONMENT.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF