Date |
Text |
2015-01-25 09:43:44 | 1) SHT. A5.0- THE ACCESSIBLE DETAILS FOR THE DRINKING |
| FOUNTAINS ARE COMPLETELY MISSING FROM THE SHEET. |
| PROVIDE FULL DETAILS .COMPLY W/ 2010 FBC, ACCESSIBILITY |
| SECS. 211, 306,& 602. |
| 2) THE TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| WASHER STANDPIPE SHALL BE A MINIMUM OF 2 INCHES IN |
| DIAMETER. THE CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM |
| OF 3 INCHES PER THE 2010 FPC SEC. 406.3.THE RISER SHOWS |
| 2 1/2". |
| 3) THERE IS STILL A DISCEPANCY BETWEEN THE SHOWER STALL |
| DIMENSIONS SHOWN ON SHT. A1.1 AND THE DIMENSIONS SHOWN |
| IN THE PLUMBING FIXTURE SCHEDULE ON SHT.P1.0. CLEARLY |
| SHOW THE INSIDE DIMENSIONS (L X W) OF THE SHOWER |
| STALLS. THE PLANS SHOW DIMENSIONS OF INSIDE THE SHOWER |
| TO THE EXTERIOR OF THE WALLS. THE MEP NARRATIVE STATES |
| THE PLUMBING FIXTURE SCHEDULE HAS THE CORRECT STALL |
| DIMENSIONS. IF THIS IS IN FACT CORRECT, ENSURE THAT THE |
| DIMENSIONS ON THE ARCHITECTURAL PLAN CORRELATE WITH THE |
| PLUMBING FIXTURE SCHEDULE. WPB AMEND. TO 2010 FBC |
| SEC.107.2.1. |
| 4) THE DEVELOPED LENGTH OF THE BRANCH VENT CONNECTING |
| THE VENT STACKS TO THE VENT THROUGH THE ROOF EXCEEDS |
| FORTY FEET IN DEVELOPED LENGTH AND SHALL BE INCREASED |
| ONE PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH OF THE |
| VENT PIPE PER THE 2010 FPC SEC.916.2, 916.4.1. THIS |
| SHALL BEGIN AT THE VENT FOR THE ACCESSIBLE SHOWER IN |
| THE WOMEN'S RESTROOM. |
| 5) THERE ARE STILL SECTIONS OF THE OF THE PLUMBING |
| RISER ON SHT. P1.0 THAT ARE NOT SIZED. CHECK THE WET |
| SECTIONS OF THE WASTE STACKS AND ALSO THE BUILDING |
| DRAIN. TYPICAL SIZES CAN BE SHOWN AS SUCH. WPB AMEND. |
| TO 2010 FBC SEC.107.2.1, TABLE 709.1. |
| 6) THE VENT FOR THE WASHING MACHINE SHALL BE A MINIMUM |
| OF 2 INCHES, NOT 1 1/2 INCHES AS SHOWN PER THE 2010 FPC |
| SEC.916.1. |
| |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |