Plan Review Notes
Plan Review Notes For Permit 14110854
Permit Number 14110854
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-29 05:02:011) SHT. A1.1 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR
 THE WATER CLOSET PER THE 2010 FL. ACCESSIBILITY CODE
 SEC. 604.3.
 2) SHT. A5.0 - THE MAXIMUM HEIGHT OF THE HAND DRYER
 ABOVE THE FINISH FLOOR SHALL BE 48 INCHES PER THE FAC
 SEC.308. THE PLAN SHOWS 48"-50".
 3) SHT. P1.0 - THE PLUMBING FIXTURE SCHEDULE SHOWS THE
 HANDICAP ACCESSIBLE SHOWER DIMENSIONS AS 38" X 37" AND
 THE STANDARD SHOWER AS 42" X 34" AND SHT. A1.1 SHOWS
 DIFFERENT DIMENSIONS FOR BOTH SHOWERS. CLARIFY.
 4) THE WASHER AND DRYER SHALL COMPLY W/2010 FAC
 SECS.611.1 - 611.4.
 5) SIZE ALL WET SECTIONS OF THE WASTE AND SOIL STACKS
 AND THE BUILDING DRAIN.COMPLY WITH FPC TABLE 710.1.(2).
 6) SIZE ALL SECTIONS OF THE VENT SYSTEM. COMPLY WITH
 FPC TABLE 916.1.
 7) SHT. P1.2 - FLOOR DRAIN DETAIL - DELETE THE
 REFERENCE TO BACKWATER VALVES. BACKWATER VALVES SHALL
 BE INSTALLED WHEN REQUIRED BY 2010 FPC SEC.715.
 8) SHT. P1.2 - WATER HEATER DETAIL - THE HOT WATER
 LINES ARE NON-CONTINUOUS AND IT IS DIFFICULT TO SEE
 WHERE THEY CONNECT TO EACH OTHER AND TO THE RECIRC
 SYSTEM AND OTHER POINTS. PROVIDE A CLEAR AND LEGIBLE
 DETAIL CLEARLY SHOWING THE CONNECTION POINTS.
 9) THE DEVELOPED LENGTH OF THE BRANCH VENT CONNECTING
 THE VENT STACKS TO THE VENT THROUGH THE ROOF EXCEEDS
 FORTY FEET IN DEVELOPED LENGTH AND SHALL BE INCREASED
 ONE PIPE SIZE PER THE 2010 FPC SEC.916.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  