2014-11-29 05:02:01 | 1) SHT. A1.1 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR |
| THE WATER CLOSET PER THE 2010 FL. ACCESSIBILITY CODE |
| SEC. 604.3. |
| 2) SHT. A5.0 - THE MAXIMUM HEIGHT OF THE HAND DRYER |
| ABOVE THE FINISH FLOOR SHALL BE 48 INCHES PER THE FAC |
| SEC.308. THE PLAN SHOWS 48"-50". |
| 3) SHT. P1.0 - THE PLUMBING FIXTURE SCHEDULE SHOWS THE |
| HANDICAP ACCESSIBLE SHOWER DIMENSIONS AS 38" X 37" AND |
| THE STANDARD SHOWER AS 42" X 34" AND SHT. A1.1 SHOWS |
| DIFFERENT DIMENSIONS FOR BOTH SHOWERS. CLARIFY. |
| 4) THE WASHER AND DRYER SHALL COMPLY W/2010 FAC |
| SECS.611.1 - 611.4. |
| 5) SIZE ALL WET SECTIONS OF THE WASTE AND SOIL STACKS |
| AND THE BUILDING DRAIN.COMPLY WITH FPC TABLE 710.1.(2). |
| 6) SIZE ALL SECTIONS OF THE VENT SYSTEM. COMPLY WITH |
| FPC TABLE 916.1. |
| 7) SHT. P1.2 - FLOOR DRAIN DETAIL - DELETE THE |
| REFERENCE TO BACKWATER VALVES. BACKWATER VALVES SHALL |
| BE INSTALLED WHEN REQUIRED BY 2010 FPC SEC.715. |
| 8) SHT. P1.2 - WATER HEATER DETAIL - THE HOT WATER |
| LINES ARE NON-CONTINUOUS AND IT IS DIFFICULT TO SEE |
| WHERE THEY CONNECT TO EACH OTHER AND TO THE RECIRC |
| SYSTEM AND OTHER POINTS. PROVIDE A CLEAR AND LEGIBLE |
| DETAIL CLEARLY SHOWING THE CONNECTION POINTS. |
| 9) THE DEVELOPED LENGTH OF THE BRANCH VENT CONNECTING |
| THE VENT STACKS TO THE VENT THROUGH THE ROOF EXCEEDS |
| FORTY FEET IN DEVELOPED LENGTH AND SHALL BE INCREASED |
| ONE PIPE SIZE PER THE 2010 FPC SEC.916.4.1. |
| |