Plan Review Notes
Plan Review Notes For Permit 14110854
Permit Number 14110854
Review Stop M
Sequence Number 1
Notes
Date Text
2015-01-03 11:08:41PLAN DENIED
 1) REFER TO SECTION 304.1 GENERAL AND
 606.2.1 SUPPLY AIR SYSTEMS FBC (M) 2010
 FOR RTU 1,2,3,4 AND 8
 2) SHOW TERMINATION OF ALL EXHAUST REFER TO
 SECTION501.2 EXHAUST DISCHARGE 2010 FBC (M)
 3) PROVIDE A DETAIL FROM THE ENGINEER FOR
 CURB TO ROOF TIE DOWN AND RTU TO CURB TIE DOWN
 301.12 WIND RESISTANCE
 4) REFER TO SECTION 1509.7 MECHANICAL UNITS
 2010 FBC
 5) DRYER BOOSTER FANS ARE NOT PERMITTED IN THE
 CITY OF WEST PALM BEACH PER FIRE DEPARTMENT.
 6) REFER TO SECTION 601.4 BALANCED RETURN AIR
 2010 FBC (M)
 7) REFER TO SECTION 603.5 NONMETALLIC DUCT
 2010 FBC (M).
  