Plan Review Notes
Plan Review Notes For Permit 14110854
Permit Number 14110854
Review Stop E
Sequence Number 1
Notes
Date Text
2015-01-08 13:53:23 
 14110854
 5335 N. MILITARY TRAIL #19
 PLANET FITNESS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS. ALL COMMENTS BASED ON THE 2008 NEC.
  
 PROVIDE AN ELECTRICAL RISER PLAN FOR THE ELECTRICAL
 SERVICE FEEDING THIS BUILDING SHOWING LOCATION OF ALL
 METERS AND MAIN DISCONNECTS. VERIFY THE ELECTRICAL
 SERVICE MAINS SERVING THIS BUILDING INCLUDING UNIT #19
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. INDICATE
 THE REQUIRED FAULT CURRENT RATING FOR ALL NEW
 EQUIPMENT. NEC 110.9, 110.10, 215.5, 230.71,
  
 THE MINIMUM SIZE EQUIPMENT GROUNDING CONDUCTOR FOR 1200
 AMPERE IS 3/0. VERIFY THE INTENDED USE AND PROPOSED
 TERMINATION POINT FOR THE 2/0 EQUIPMENT GROUND ROUTED
 WITH THE SERVICE CONDUCTORS. NEC T. 250.122
  
 INDICATE THE SIZE AND TYPE OF GROUNDING ELECTRODE
 PROPOSED FOR THIS SERVICE. NEC 250.32, 250.52
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22
  
 PROVIDE DEDICATED SPACE FOR THE ELECTRICAL DISCONNECTS
 AND PANEL BOARDS. NEC 110.26, 240.24(D)
  
 ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING
 AND SIGN CIRCUIT. PROVIDE SHOW WINDOW LIGHTING OUTLETS.
 NEC 210.62, 408.4, 600.5
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE A STRUCTURAL DETAIL FOR HANGING THE TWO LARGE
 CEILING FANS. FBC 1604.1
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW