Date |
Text |
2014-12-09 15:17:01 | BUILDING PLAN REVIEW |
| PERMIT: 14110854 |
| ADD: 5335 N. MILITARY TRAIL |
| CONT: TO BE DETERMINED |
| TEL: (561 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 09/ 2014 |
| ACTION: DENIED |
| |
| 1) BOTH SHEETS EG1.0 & A1.0 BOTH INDICATE THE TENANT |
| SEPARATION WALL TO BE A 1 HOUR TENANT SEPARATION WALL. |
| THE PLANS FAIL TO IDENTIFY WHAT TYPE OF OCCUPANCY IS ON |
| BOTH SIDES OF THE A3 OCCUPANCY. 2010 FBC-B TABLE 508.4 |
| |
| 2) THE COVERSHEET T.1.0 INDICATES THIS SPACE TO BE FIRE |
| SPRINKLERED, BUT NO PLANS WERE SUBMITTED. UNDER THE |
| 2010 FBC-B TABLE 508.2.5 INCIDENTAL ACCESSORY |
| OCCUPANCIES LAUNDRY ROOMS OVER 100 SQ. FT. HAVE TO BE |
| EITHER 1 HOUR FIRE RATED OR FIRE SPRINKLERED. TO TAKE |
| THE CREDIT THE CODE GIVES FOR FIRE SPRINKLERS PLANS |
| HAVE TO BE SUBMITTED. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: (5.) FIRE SUPPRESSION |
| SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE SPRINKLERS |
| |
| 3) SHEET A1.0 INDICATES IN THE LOCKER ROOMS ACCESSIBLE |
| LOCKERS, SHEET A5.0 SHOWS DETAILS FOR ACCESSIBLE |
| BENCHES, THEY ARE MISSING ON THE A1.0 LOCKER ROOM |
| DETAILS. SEE 2010 FBC-ACCESSIBILITY CODE 903.1-4 . |
| |
| 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |