2015-02-19 12:40:321) THE MATCH LINES ADDED ON SHEETS P201 THRU P206 HAVE
 NOT ACCOMPLISHED THE INTENT FOR CLARIFICATION.THE ADDED
 NOTE"SEE FLOOR PLAN 101 FOR CONTINUATION" REFERENCES
 THE CORRECT SHEET BUT SHEET 101 DOES NOT SHOW THE
 CONTINUATION OF THE PIPING FOR THE DIFFERENT AREAS.
 ALTHOUGH I APPLAUD THE EFFORT TO CLARIFY DETAILS, THE
 CHANGES HAVE CAUSED ADDITIONAL CONFUSION. SHT. P101
 SHOWS VERY LITTLE PIPNG, AND ROOMS/AREAS ARE NOT
 NUMBERED, SO IT IS VERY DIFFICULT TO LOCATE THE
 CONTINUATION OF PIPNG FROM ONE SHEET OR AREA TO THE
 NEXT. THE MATCH LINES ARE NOT IDENTIFIED WITH A LETTER
 OR NUMBER SO IT IS VERY DIFFICULT TO FOLLOW THE PIPING
 SYSTEMS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT.P3.04 - IN MY PREVIOUS PLAN REVIEW, COMMENT #
 11, I REQUESTED TO SHOW THE CONTINUATION / CONNECTION
 POINTS OF THE 2" & 3" VENTS ON THE GREASY WASTE
 SYSTEM.THE NOTE "SEE PLANS FOR CONTINUATION" DOES NOT
 PROVIDE MUCH HELP.IF THE SPECIFIC PLAN COULD BE
 IDENTIFIED FOR WHERE THESE VENTS CONNECT I COULD LOCATE
 & REVIEW THESE ITEMS MUCH QUICKER.
 3) SHT. P3.04 - THERE IS A SECTION OF VENT THAT GOES
 NOWHERE. IT APPEARS TO BE A TYPO ERROR.
  
 PLEASE CONTACT ME SO WE CAN SET UP A MEETING TO DISCUSS
 THESE COMMENTS.
  