Date |
Text |
2014-12-20 13:34:26 | 1)SHT. GI 101 - PLUMBING FIXTURE COUNT - THE CHART |
| SHOWS "0"REQUIRED URINALS FOR THE ASSEMBLY AND BUSINESS |
| OCCUPANCIES BUT ALSO SHOWS 11 PROVIDED. CLARIFY.THE |
| TABLE READS THAT 67% MAXIMUM SUBSTITUTION FOR THE |
| BUSINESS OCCUPANCY. THE BOX SHOULD READ 50% |
| SUBSTITUTION TO CORRELATE WITH NOTE #2 AND THE FL. |
| PLUMBING CODE SEC.419.2. |
| 2) SHT. P1.02 - 4" STORM RISER UP TO THE DECK DRAIN - |
| THE MAXIMUM SQUARE FOOTAGE A HORIZONTAL 4" STORM DRAIN |
| CAN ACCOMMODATE IS 1504 SQUARE FEET AT AN 1/8" SLOPE |
| PER TABLE 1106.3 OF THE 2010 FL. PLBG. CODE. INDCATE |
| THE SLOPE OF THE STORM DRAIN. |
| 3) SHT.P1.03 - SHOW THE SQUARE FOOTAGE DRAINING INTO |
| EACH STORM RISER AND ALSO THE SQUARE FOOTAGE THAT THE |
| 6" & 8" HORIZONTAL STORM DRAINS ARE CARRYING. COMPLY |
| WITH TABLE 1106.3 OF THE FPC. |
| 4) SUBMIT MANUFACTURER SPECIFICATIONS/INSTALLATION |
| MANUAL FOR THE OIL SENSING SUMP PUMP. WPB AMEND. TO |
| 2010 FBC SEC. 107.2.1. |
| 5) THERE IS NOLOWER LEVEL NORTH PLUMBING PLAN IN THIS |
| REVISION SUBMITTAL. CLARIFY. |
| 6 )SHT. P2.02 - PROVIDE A MATCH LINE ON THE LEFT SIDE |
| (SW SIDE) OF THE PLAN FOR THE CONTINUATION OF THE |
| PLUMBING SYSTEM. DO THE SAME FOR ALL SHEETS.WPB AMEND. |
| TO 2010 FBC SEC. 107.2.1. |
| 7) SHT. P2.02 - REFERS TO AN ENLARGED PLAN #2 ON SHT. |
| P.206 FOR CONTINUATION OF PLUMBING WATER LINES. THE |
| ENLARGED PLAN #2 ON P2.06 DOES NOT CORRELATE WITH THE |
| AREA ON P2.02. THE ENLARGED PLAN #2 IS FOR CAFETERIA |
| #137 AND P2.02 IS FOR THE MAIN KITCHEM #135. |
| 8) SHT. P2.04 - THE BOTTOM FED WATER HEATERS SHALL BE |
| EQUIPPED WITH VACUUM RELIEF VALVES PER 2010 FPC SEC. |
| 504.2. |
| 9) SHT. P2.06 - REFERS TO SHT. P2.02 FOR THE |
| CONTINUATION OF PLUMBING FOR THE EMPLOYEE CAFETERIA |
| #137.THIS AREA IS NOT SHOWN ON SHT.P2.02. CLARIFY. |
| 10) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE |
| CONTINUATION OF SERVICE LINES FOR THE PLUMBING. WILL |
| THESE REVISIONS TO THE PLUMBING / GAS SYSTEMS AFFECT |
| THEIR LOCATIONS SHOWN ON THE CIVIL DRAWINGS? IF SO , |
| SUBMIT REVISED CIVIL DRAWINGS FOR REVIEW. |
| 11) SHT. P3.04 - SHOW THE CONTINUATION/ CONNECTION |
| POINTS OF THE 2" & 3" VENTS ON THE GREASY WASTE SYSTEM. |
| WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 12) SHT.P3.04 - RISER "E" - THE FLOOR DRAINS APPEAR TO |
| BE MORE THAN 12 FEET FROM A VENT/VENTED LINE. SEE TABLE |
| 906.1.2010 FPC. THERE ARE OTHER FIXTURE DRAINS THAT ARE |
| ALSO IN VIOLATION. |
| 13) SHT.S 201 - ELEVATOR PIT SECTION DETAIL#14 - THE |
| DEPTH OF THE SUMP PIT SHALL BE A MIN. OF 23 INCHES PER |
| 2010 FPC SEC.712.3.2. |
| **NOTE** - IT WOULD BE MUCH EASIER TO LOCATE AND |
| SPECIFY THE AREAS OF THE DEFICIENCIES ON THE ENLARGED |
| PLANS IF ALL THE GRID LINES WERE IDENTIFIED ON THE |
| PLANS. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |