Plan Review Notes
Plan Review Notes For Permit 14110818
Permit Number 14110818
Review Stop P
Sequence Number 1
Notes
Date Text
2014-12-20 13:34:261)SHT. GI 101 - PLUMBING FIXTURE COUNT - THE CHART
 SHOWS "0"REQUIRED URINALS FOR THE ASSEMBLY AND BUSINESS
 OCCUPANCIES BUT ALSO SHOWS 11 PROVIDED. CLARIFY.THE
 TABLE READS THAT 67% MAXIMUM SUBSTITUTION FOR THE
 BUSINESS OCCUPANCY. THE BOX SHOULD READ 50%
 SUBSTITUTION TO CORRELATE WITH NOTE #2 AND THE FL.
 PLUMBING CODE SEC.419.2.
 2) SHT. P1.02 - 4" STORM RISER UP TO THE DECK DRAIN -
 THE MAXIMUM SQUARE FOOTAGE A HORIZONTAL 4" STORM DRAIN
 CAN ACCOMMODATE IS 1504 SQUARE FEET AT AN 1/8" SLOPE
 PER TABLE 1106.3 OF THE 2010 FL. PLBG. CODE. INDCATE
 THE SLOPE OF THE STORM DRAIN.
 3) SHT.P1.03 - SHOW THE SQUARE FOOTAGE DRAINING INTO
 EACH STORM RISER AND ALSO THE SQUARE FOOTAGE THAT THE
 6" & 8" HORIZONTAL STORM DRAINS ARE CARRYING. COMPLY
 WITH TABLE 1106.3 OF THE FPC.
 4) SUBMIT MANUFACTURER SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL SENSING SUMP PUMP. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 5) THERE IS NOLOWER LEVEL NORTH PLUMBING PLAN IN THIS
 REVISION SUBMITTAL. CLARIFY.
 6 )SHT. P2.02 - PROVIDE A MATCH LINE ON THE LEFT SIDE
 (SW SIDE) OF THE PLAN FOR THE CONTINUATION OF THE
 PLUMBING SYSTEM. DO THE SAME FOR ALL SHEETS.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SHT. P2.02 - REFERS TO AN ENLARGED PLAN #2 ON SHT.
 P.206 FOR CONTINUATION OF PLUMBING WATER LINES. THE
 ENLARGED PLAN #2 ON P2.06 DOES NOT CORRELATE WITH THE
 AREA ON P2.02. THE ENLARGED PLAN #2 IS FOR CAFETERIA
 #137 AND P2.02 IS FOR THE MAIN KITCHEM #135.
 8) SHT. P2.04 - THE BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED WITH VACUUM RELIEF VALVES PER 2010 FPC SEC.
 504.2.
 9) SHT. P2.06 - REFERS TO SHT. P2.02 FOR THE
 CONTINUATION OF PLUMBING FOR THE EMPLOYEE CAFETERIA
 #137.THIS AREA IS NOT SHOWN ON SHT.P2.02. CLARIFY.
 10) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE
 CONTINUATION OF SERVICE LINES FOR THE PLUMBING. WILL
 THESE REVISIONS TO THE PLUMBING / GAS SYSTEMS AFFECT
 THEIR LOCATIONS SHOWN ON THE CIVIL DRAWINGS? IF SO ,
 SUBMIT REVISED CIVIL DRAWINGS FOR REVIEW.
 11) SHT. P3.04 - SHOW THE CONTINUATION/ CONNECTION
 POINTS OF THE 2" & 3" VENTS ON THE GREASY WASTE SYSTEM.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 12) SHT.P3.04 - RISER "E" - THE FLOOR DRAINS APPEAR TO
 BE MORE THAN 12 FEET FROM A VENT/VENTED LINE. SEE TABLE
 906.1.2010 FPC. THERE ARE OTHER FIXTURE DRAINS THAT ARE
 ALSO IN VIOLATION.
 13) SHT.S 201 - ELEVATOR PIT SECTION DETAIL#14 - THE
 DEPTH OF THE SUMP PIT SHALL BE A MIN. OF 23 INCHES PER
 2010 FPC SEC.712.3.2.
 **NOTE** - IT WOULD BE MUCH EASIER TO LOCATE AND
 SPECIFY THE AREAS OF THE DEFICIENCIES ON THE ENLARGED
 PLANS IF ALL THE GRID LINES WERE IDENTIFIED ON THE
 PLANS.
  
 PLUMBING PLAN REVIEW