Plan Review Notes
Plan Review Notes For Permit 14110818
Permit Number 14110818
Review Stop G
Sequence Number 1
Notes
Date Text
2014-12-21 06:23:18SHT.P306 -
 1) SHOW THE LINE SIZE DOWNSTREAM OF THE 2 PSI PRESSURE
 REGULATOR AT THE MAIN INTO THE STRUCTURE THAT SUPPLIES
 6765 CFH OF GAS. IF THIS IS 2 " THE LINE IS UNDERSIZED
 FOR THE BTU LOAD AND A TOTAL DISTANCE OF 255 FT. ( THE
 300 FEE TCOLUMN WILL GOVERN ). PER THE 2010 FLORIDA GAS
 CODE TABLE 402.4 (3) THE MINIMUM SIZE SHALL BE 2 1/2 "
 TO SUPPLY THE 6765 BTU LOAD.
 2) GENERAL NOTE # 1 REFERS TO THE SIZING EQUATION FROM
 THE FGC. IF THE EQUATIONS WERE USED IN THE SIZING OF
 THIS GAS SYSTEM, SUBMIT THE CALCULATIONS TO SUPPORT THE
 PIPE SIZING. WPB AMEND. TO 2010 FBC SEC.107.2.1. & FGC
 SEC. 402.4.
 3) PLEASE REFERENCE ALL APPLICABLE TABLES FROM THE 2010
 FGC UTILIZED FOR THE SIZING OF THE SYSTEM IN THE
 GENERAL NOTES SECTION. FGC SEC.402.4.
 4) THE SECTION OF GAS LINE SUPPLYING 6215 BTU'S IS
 UNDERSIZED IF BASED ON TABLE 402.4 (3) OF THE GAS CODE.
 THE MAXIMUM ALLOWED BTU LOAD ON A 2 " PIPE AT 300 FT.
 IS 5600 CFH @ 2 PSI. THE LINE SHALL BE 2 1/2 ".
 5) THE 1 1/4" LINE SUPPLYING 2162 CFH IS UNDERSIZED.
 THE MAXIMUM ALLOWED BTU LOAD ON AN 1 1/4" PIPE AT 300
 FT. IS 1940 CFH @ 2PSI. THE LINE SHALL BE 1 1/2".
 6) LOWER KITCHEN # 135 GAS RISER - SHOW THE TOTAL
 DISTANCE FROM THE STEP DOWN REGULATOR TO THE MOST
 REMOTE OUTLET. AS DRAWN IT IS DIFFICULT TO DETERMINE
 WHERE EACH LENGTH APPLIES TO EACH SECTION. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SHOW THE TOTAL LENGTH OF THE 1 1/2" PIPE RUN FROM
 THE STEP DOWN REGULATOR TO THE GWH-1.
 8) SHOW THE TOTAL LENGTH OF THE 1 1/2" PIPE RUN FROM
 THE STEP DOWN GENERATOR TO THE GWH-2.
 9) THE 1" LINE SUPPLYING 1088 CFH IS UNDERSIZED.THE
 MAXIMUM ALLOWED BTU LOAD ON A 1" LINE AT 300 FT. IS 945
 CFH @ 2 PSI. THE LINE SHALL BE 1 1/4". TABLE 402.4 (3).
 10) THE 1 1/2" LINE SUPPLYING 2965 CFH IS UNDERSIZED..
 THE MAXIMUM ALLOWED BTU LOAD ON AN 1 1/2" LINE AT 300
 FT. IS 2910 CFH @ 2 PSI. THE LINE SHALL BE 2". TABLE
 402.4 (3).
 11) THE 1 1/4" GAS LINE SUPPLYING 2465 CFH IS
 UNDERSIZED. THE MAXIMUM ALLOWED BTU LOAD ON AN 1 1/4"
 LINE AT 300 FT. IS 1940 CFH @ 2 PSI. THE LINE SHALL BE
 1 1/2". TABLE 402.4 (3).
 12) GAS RISER # 1 KIT. #245 - SHOW THE TOTAL RUN OF
 PIPE FROM THE STEP DOWN REGULATOR TO THE MOST REMOTE
 OUTLET. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 13) GAS RISER #2 KIT.#245 - SHOW THE TOTAL RUN OF PIPE
 FROM THE STEP DOWN REGULATOR TO THE MOST REMOTE OUTLET.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) CLARIFY THE CONNECTION POINT OF THE BRANCH LINE FOR
 THE BUFFET SERVICE 2 - #266 GAS RISER TO THE MAIN. IT
 APPEARS TO BE CONNECTED TO THE LOW PRESSURE LINE BUT IT
 ALSO APPEARS TO BE INDICATED AS A MEDIUM PRESSURE (2
 PSI) LINE. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  