Notes |
Date |
Text |
2014-11-22 10:53:17 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) THE ONE STORY STRUCTURE IS LOCATED IN EXPOSURE | | CATEGORY C WITH A WINDSPEED OF 170 MPH VULT. THE | | REQUIRED UPLIFT PRESSURES FOR ROOF ZONE 3 ON THE FLAT | | ROOF EXCEEDS THE -90 PSF MAXIMUM DESIGN PRESSURE FOR | | THE PROPOSED ROOFING SYSTEM FROM THE ROOFING PRODUCT | | APPROVAL, FL1654. SPECIFY A SYSTEM WITH ADEQUATE DESIGN | | PRESSURES. FBC-R 301.1 | | | | 2) SUBMIT TWO COPIES OF A ROOF DIAGRAM OF THE BUILDING | | WITH DIMENSIONS AND INDICATE THE AREA THAT IS TO BE | | RE-ROOFED. FBC 107.2.1 | | | | 3) PRODUCT APPROVAL NOA NO. 12-0327.02 HAS BEEN | | SUPERSEDED. SUBMIT TWO CURRENT PRODUCT APPROVALS FOR | | THE A/C ROOF STANDS PER DCA RULE 9N-3. | | | | 4) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING ON THE | | PLANS. FBC 107.2.1 & FBC-R 301.1 | | | | | | |
|