Plan Review Notes For Permit 14110720 |
Permit Number |
14110720 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-04 18:37:49 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FBC 2010 RESIDENTIAL 301, FASTENING PROPOSED DOES | | NOT MEET THE REQUIREMENTS OF THE PRODUCT APPROVAL. | | | | "SHUTTER CONNECTION MOUNTING TYPE" COLUMN ON THE | | INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE NAMING | | CONVENTION IN THE PRODUCT APPROVAL. SEE SHEETS 14 AND | | 15. "WALL MOUNT" IS PROPOSED. ON SHEETS 14 AND 15, | | CONNECTION TYPES "H" AND "K" ARE CIRCLED. PLEASE REVISE | | THIS COLUMN TO CORRELATE WITH THE PRODUCT APPROVAL. | | | | 2. CONNECTION TYPE K IS A FLOOR MOUNT AND REQUIRES A | | CONCRETE SUBSTRATE. "CONCRETE BLOCK" IS STATED AS THE | | SUBSTRATE ON THE INSTALLATION SCHEDULE. A FLOOR IS | | TYPICALLY FORMED AND POURED CONCRETE. PLEASE CLARIFY, | | OR REVISE EITHER CONNECTION TYPE AND/OR SUBSTRATE. | | | | 3. THE ITEMS CIRCLED ON THE PRODUCT APPROVAL APPEAR TO | | INDICATE CONNECTION TYPE "H" WITH 10" SPACING CIRCLED | | AT THE TOP, BUT THIS IS A FLOOR CONNECTION (CAN ONLY BE | | USED AT THE FLOOR). | | | | "K" IS ALSO CIRCLED WITH 7" SPACING, APPEARS TO BE THE | | BOTTOM CONNECTION TYPE, SEE ITEM 2 REGARDING SUBSTRATE. | | | | PROPOSED INSTALLATION IS NOT CLEAR; COMPLIANCE CANNOT | | BE DETERMINED. | | |
|