Plan Review Notes
Plan Review Notes For Permit 14110715
Permit Number 14110715
Review Stop E
Sequence Number 1
Notes
Date Text
2014-11-25 11:25:4111/25/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE WIND LOAD CALCULATIONS FOR ALL RELOCATED BASES
 AND LIGHT POLES INCLUDING LUMINAIRE(S) IN COMPLIANCE
 WITH THE FBC 1609
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  