| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| ELECTRICAL PLAN REVIEW |
| ACTION: |
| |
| 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| ASTRONOMICAL TIME SWITCH. |
| |
| 2) 2010 FBC-BUILDING SECTION 1609 |
| PROVIDE WIND LOAD CALCULATIONS FOR ALL RELOCATED BASES |
| AND LIGHT POLES INCLUDING LUMINAIRE(S) IN COMPLIANCE |
| WITH THE FBC 1609 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |