Plan Review Notes For Permit 14110637 |
Permit Number |
14110637 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-01-24 08:10:40 | PLAN DENIED | | 1) PROVIDE A DETAIL FROM THE ENGINEER ON HOW | | THE RTU CURB IS ANCHORED TO THE ROOF PER | | SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | 2) FRESH AIR CALCULATIONS PER TABLE 403.3 | | MINIMUM VENTILATION RATES 2010 FBC (M) | | 3) PROVIDE ENERGY CALCULATIONS PER SECTION | | 503.2.1 CALCULATION OF HEATING AND COOLING | | 2010 FLORIDA ENERGY CODE. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|