Plan Review Notes
Plan Review Notes For Permit 14110637
Permit Number 14110637
Review Stop M
Sequence Number 2
Notes
Date Text
2015-01-24 08:10:40PLAN DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER ON HOW
 THE RTU CURB IS ANCHORED TO THE ROOF PER
 SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 2) FRESH AIR CALCULATIONS PER TABLE 403.3
 MINIMUM VENTILATION RATES 2010 FBC (M)
 3) PROVIDE ENERGY CALCULATIONS PER SECTION
 503.2.1 CALCULATION OF HEATING AND COOLING
 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676