2014-11-22 06:23:28 | 1) SHT. A-5 - TOILET ELEVATION - 1/A-1 - THE TOP OF THE | | TOILET FROM THE FININSHED FLOOR TO THE SEAT SHALL BE | | 17-19 INCHES MAXIMUM TO THE TOP OF THE SEAT PER 2010 | | FAC SEC. 604.4 NOT 19-20 INCHES AS SHOWN. | | 2) THE CLEAR KNEE SPACE UNDER THE LAVATORY SHALL BE 27 | | INCHES PER FAC SEC.306.3. SHT. A-5. | | 3) SHT. A-5 - THE TOILET PAPER DISPENSER SHALL BE 7-9 | | INCHES IN FRONT OF THE WATER CLOSET MEASURED TO THE | | CENTERLINE OF THE DISPENSER PER FAC SEC.604.7. | | 4) SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | INSTANTANEOUS WATER HEATER.WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | 5) SHT.P2.1B - CLARIFY "EXISTING TUB TO BE REMOVED." | | THERE IS NO TUB SHOWN ON SHT. A-1.2. | | 6) SUBMIT A SANITARY AND WATER RISER FOR ALL NEW WORK | | TO BE INSTALLED. WPB AMEND. TO 2010 FBC | | SEC.107.3.5.1.3. | | 7) KITCHEN SINK/COUNTER SHALL COMPLY W/FAC SEC.212.3 & | | 804. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|