Plan Review Notes
Plan Review Notes For Permit 14110637
Permit Number 14110637
Review Stop M
Sequence Number 1
Notes
Date Text
2014-11-25 14:51:24PLAN DENIED
  
 1) FRESH AIR DAMPER REQUIRED AT EACH UNIT
 503.2.4.4 SHUT OFF DAMPER CONTROL 2010 FLORIDA ENERGY
 CODE
 2) REFER TO SECTION 503.2.1 CALCULATION OF HEATING AND
 COOLING
 LOADS 2010 FLORIDA ENERGY CODE
 3) PROVIDE EQUIPMENT SCHEDULE ON THE PLAN SECTION
 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  