Plan Review Notes
Plan Review Notes For Permit 14110622
Permit Number 14110622
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-26 08:23:111) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
 2) THE SHOWER SHALL HAVE BACKING FOR GRAB BARS
 INSTALLED PER THE 2010 FL. ACCESSIBILITY CODE
 SEC.608.3.
 3) THE LOCATION OF THE CONTROLS IN THE SHOWER SHALL
 COMPLY WITH SEC.608.5 OF THE 2010 FAC.
 4) SHOW THE INSIDE DIMENSIONS OF THE SHOWER (L X W ).
 COMPLY WITH2010 FAC SEC.608.2.2, 608.2.3.
 5) SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE PLAN FOR
 THE WATER CLOSET AND LAVATORY PER 2010 FAC SECS. 604.3
 & 606.2.
 6) SHT. 1 - SHOW THE HEIGHT OF THE GRAB BARS ABOVE THE
 FINISHED FLOOR. COMPLY WITH 2010 FAC SEC.609.4. THE
 HEIGHT IS OBSCURED ON THE PLAN BY PRINTING.
 7) SHOW THE LOCATION OF THE TOILET SEAT ABOVE THE
 FINISHED FLOOR PER 2010 FAC SEC. 604.4. THE DIMENSION
 IS OBSCURED BY PRINTING.
 8) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS
 OCCUPANCY PER TABLE 403.1 OF THE FL PLUMBING CODE.
 INDICATE ON THE PLAN IF THERE IS AN EXISTING DRINKING
 FOUNTAIN IN THE BUILDING THAT COMPLIES WITH THE FLORIDA
 ACCESSIBILITY CODE.
 9) THE TOILET ROMM APPEARS TO BE LOCATED ON THE 2ND
 FLOOR OF THIS BUILDING YET THE PLANS DO NOT NOT SHOW
 ANY MEANS OF ACCESS TO THE 2ND FLOOR. THE 2ND FLOOR
 OFFICE AND BATHROOM SHALL BE ACCESSIBLE PER THE FAC
 SEC.201.1.1, 213.1, 213.2, 213.3.6, AND VERTICAL
 ACCESSIBILITY SHALL BE PROVIDED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  