2014-11-26 08:23:11 | 1) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010 |
| FBC SEC. 107.3.5.1.3. |
| 2) THE SHOWER SHALL HAVE BACKING FOR GRAB BARS |
| INSTALLED PER THE 2010 FL. ACCESSIBILITY CODE |
| SEC.608.3. |
| 3) THE LOCATION OF THE CONTROLS IN THE SHOWER SHALL |
| COMPLY WITH SEC.608.5 OF THE 2010 FAC. |
| 4) SHOW THE INSIDE DIMENSIONS OF THE SHOWER (L X W ). |
| COMPLY WITH2010 FAC SEC.608.2.2, 608.2.3. |
| 5) SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE PLAN FOR |
| THE WATER CLOSET AND LAVATORY PER 2010 FAC SECS. 604.3 |
| & 606.2. |
| 6) SHT. 1 - SHOW THE HEIGHT OF THE GRAB BARS ABOVE THE |
| FINISHED FLOOR. COMPLY WITH 2010 FAC SEC.609.4. THE |
| HEIGHT IS OBSCURED ON THE PLAN BY PRINTING. |
| 7) SHOW THE LOCATION OF THE TOILET SEAT ABOVE THE |
| FINISHED FLOOR PER 2010 FAC SEC. 604.4. THE DIMENSION |
| IS OBSCURED BY PRINTING. |
| 8) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS |
| OCCUPANCY PER TABLE 403.1 OF THE FL PLUMBING CODE. |
| INDICATE ON THE PLAN IF THERE IS AN EXISTING DRINKING |
| FOUNTAIN IN THE BUILDING THAT COMPLIES WITH THE FLORIDA |
| ACCESSIBILITY CODE. |
| 9) THE TOILET ROMM APPEARS TO BE LOCATED ON THE 2ND |
| FLOOR OF THIS BUILDING YET THE PLANS DO NOT NOT SHOW |
| ANY MEANS OF ACCESS TO THE 2ND FLOOR. THE 2ND FLOOR |
| OFFICE AND BATHROOM SHALL BE ACCESSIBLE PER THE FAC |
| SEC.201.1.1, 213.1, 213.2, 213.3.6, AND VERTICAL |
| ACCESSIBILITY SHALL BE PROVIDED. |
| |