Date |
Text |
2014-12-17 13:34:38 | 12/17/2014 |
| PROJECT: ADDITION 5913 S. DIXIE |
| PERMIT#: 14110622 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED. |
| |
| 1) FBC-WPB AMENDMENTS 107.3.5.1.2. MINIMUM ELECTRICAL |
| PLAN REVIEW CRITERIA SHALL INCLUDE BUT NOT BE LIMITED |
| TO THE FOLLOWING: |
| "SERVICES" A SITE PLAN INDICATING THE LOCATION OF THE |
| ELECTRICAL UTILITY, DISCONNECT(S) AND PANEL(S). "WIRING |
| MEATHODS AND MATERIALS" PROVIDE A DETAILED FLOOR PLAN |
| INDICATING ALL BRANCH CIRCUIT WIRING WITH NUMBERED |
| CIRCUITRY ON THE FLOOR PLAN AND CEILING PLAN. |
| |
| 2) REVISE THE LIGHTING PLAN TO INDICATE COMPLIANCE WITH |
| THE FBC-E 505.2 |
| |
| 3) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. NEC 700.12(F) REVISE PANEL SCHEDULE AND FLOOR |
| PLAN TO INDICATE COMPLIANCE. |
| A.) EMERGENCY LIGHTING SYSTEMS SHALL BE DESIGNED AND |
| INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL |
| LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP, |
| CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES |
| EMERGENCY ILLUMINATION. NEC 700.16 REVISE PANEL |
| SCHEDULE AND FLOOR PLAN TO INDICATE COMPLIANCE. |
| |
| 4) SEE BUILDING REVIEW COMENTS. |
| ONCE A MORE DETAILED SIGNED SEALED SET OF CONSTRUCTION |
| DOCUMENTS IS SUBMITTED A MORE COMPREHENSIVE REVIEW OF |
| THE ELECTRICAL SYSTEM CAN BE COMPLETED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |