Plan Review Notes
Plan Review Notes For Permit 14110622
Permit Number 14110622
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-03 17:09:31BUILDING PLAN REVIEW
 PERMIT: 14110622
 ADD: 5935 S DIXIE HWY
 CONT: ABACOA CONSTRUCTION
 TEL: (561)249-1212
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 03/2014
 ACTION: DENIED
  
 1) SHEET # 1;
 1A) PLEASE SEE THE CODE SUMMARY UNDER THE HEADING 2.2
 THE PLANS INDICATE A NON-SPRINKLERED BUILDING - NFPA
 13. PLEASE SEE GENERAL BUILDING CODE ANALYSIS THE PLANS
 INDICATE THE TRAVEL DISTANCE FOR A BUSINESS OCCUPANCY
 OF 200 FT. FBC-B TABLE 1016.1 ALLOWS 300 FT. TRAVEL
 DISTANCE. THERE ARE DISCREPANCIES IN THE PLANS, UNABLE
 TO DETERMINE IF THE BUILDING IS FIRE SPRINKLERED OR
 NOT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS ( 5.) FIRE SUPPRESSION
 SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
  
 1B) THE TITLEBLOCK FOR THIS SHEET INDICATES, FLOOR PLAN
 W/ LIFE SAFETY. THE PLANS DO NOT INCLUDE ANY ELEMENTS
 FOR LIFE SAFETY!!!!!!!!!
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS
 (7). OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 1C) FLOOR AREA TABULATIONS;
 1ST FLOOR UNDER AIR 3901
  
 2ND FLOOR EXIST A/C 3505
 2ND FL ADDITION 488
 --------------
 SUM OF 2ND FL IS 3993 SQ FT, GREATER THAN THE FOOT
 PRINT OF 1ST FLOOR, WHERE DOES THE 2ND FLOOR OVERHANG
 THE 1ST FLOOR? NO SURVEY OR SITE PLAN WAS SUBMITTED, AT
 THIS TIME WE CAN NOT DETERMINE IF THIS EFFECTS EXTERIOR
 FIRE RESISTANCE RATINGS OF THE BUILDING, FBC-B TABLE
 602 AND OPENING PROTECTIVES UNDER FBC-B TABLE 708.5 &
 3202.2. DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.
  
 A THROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 2) THE 2010 FBC-EXISTING BUILDING CODE 1003.2
 ADDITIONAL GRAVITY LOADS. EXISTING STRUCTURAL ELEMENTS
 SUPPORTING ANY ADDITIONAL GRAVITY LOADS AS A RESULT OF
 ADDITIONS SHALL COMPLY WITH THE FLORIDA BUILDING CODE,
 BUILDING. THE ADDITION WILL IMPOSE LOADS ON SOME
 PORTION OF THE EXISTING BUILDING STRUCTURE THAT EXCEEDS
 THE CAPACITY OF THE MEMBER AND REQUIRE REINFORCEMENT OR
 OTHER MITIGATION. WHERE THE ADDITION RESULTS IN A NET
 INCREASE IN GRAVITY LOADS THAT IS SUPPORTED BY THE
 EXISTING STRUCTURE, THE AFFECTED STRUCTURAL COMPONENTS
 MUST BE CHECKED TO VERIFY THEY SATISY THE REQUIREMENTS
 OF THE CODE FOR A NEW STRUCTURE.
 THE EXISTING 1ST FLOOR ROOF TRUSSES WOULD HAVE BEEN
 DESIGNED WITH A LIVE LOAD OF 20 TO 30 PSF LIVE LOADS,
 THE LIVE LOADS FOR THE SAME EXISTING TRUSS SYSTEM
 USED AS A FLOOR SYSTEM WILL BE PER FBC-B TABLE (25)
 OFFICES 50 PSF. THIS IS OVER THE 5% ALLOWABLE
 EXCEPTION.
  
 3) THE PLANS SHEET A2 DO NOT PROVIDE WHAT WAY THE ROOF
 IS TO SLOPE, WHAT THE ROOF PITCH WILL BE THE SIZE OF
 THE SCUPPERS AND THE EMEERGENCY OVER FLOW SCUPPERS ARE?
 FBC-B 1503.4.2/ 1503.4.2.1 OVERFLOW SCUPPERS.
  
 4)SHEET A2. 1503.5 ROOF VENTILATION. ATTIC VENTILATION
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 1203.2 AND
 THE MANUFACTURER?S INSTALLATION INSTRUCTIONS.
  
 5) ONLY ONE SET OF ENERGY CALCULATIONS. THE PLANS ALSO
 DO NOT PROVIDE COMPLIANCE WITH THE ENERGY CODE THE
 MANDATORY PROVISONS FOR THE THERMO ENVELOPE.ENERGY CODE
 502.1. BUILDINGS, RENOVATIONS AND ALTERATIONS. THE
 BUILDING THERMAL ENVELOPE SHALL MEET THE REQUIREMENTS
 OF TABLE 502.1.1.1(2).
  
 6) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) ONLY ONE SET OF PRODUCT APPROVALS. COMPONENTS &
 CLADDING PRESSURES POSITVE & NEGATIVE TABLE 1609.2(2) .
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS & MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES- IDENTIFY
 SUB-SYSTEMS, EACH SUB-SYSTEM HAS THEIR OWN DESIGN
 PRESSURES AND LIMITATIONS.
  
 7) SHEET # 1 ACCESSIBLITY;
  
 7A) THE ACCESSIBILITY DETAIS ON THIS SHEET WILL NEED TO
 SHOW COMPLIANCE WITH 2010 FL ACCESS. CODE GRAB BARS,
 609.8 STRUCTURAL STRENGTH.
 ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS
 USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS
 (1112 N) IS APPLIED AT ANY POINT ON THE GRAB BAR,
 FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 7B) THE ADDITION BATHROOM AND ACCESSIBLE RESTROOM
 DETAIL WILL NOT MEET THE SIDE WALL GRAB BAR
 REQUIREMENTS, OF 2010 FL ACCESS. CODE 604.5.1 THE SIDE
 WALL GRAB BAR IS TO BE LOCATED AT 12 INCHES OFF THE
 CORNER, 42 INCHES LONG AND EXTENDING 54 INCHES FROM THE
 REAR WALL. IT APPEARS IN BOTH DETAILS THE GRAB BAR IS
 JAMBED IN THE CORNER, IT WILL BE OUT IN THE DOORWAY IF
 START POINT IS 12 INCHES FROM THE CORNER AND FROM THE
 REAR WALL.
  
 7C) THE ACCESSIBLE ELEVATION DETAIL, PLEASE PROVIDE THE
 HEIGHT REQUIREMENTS FOR THE WATER CLOSET, THE
 DIMENSIONS ARE ILLEGIBLE, FL ACCESS. CODE 604.2.
  
 7D) PLEASE SHOW SHOWER CONTROLS AND GRAB BAR LOCATIONS
 FOR SHOWER. FL ACCESS. CODE 608.3.
  
 7E) PLEASE PROVIDE THE CLEAR FLOOR SPACE REQUIREMENT FL
 ACCESS. CODE 604.3.2 OVERLAP, IN THE DETAILS IT APPEARS
 THE LAVATORY IS LOCATED WITHIN THE REQUIRED 60 INCH
 CLEAR FLOOR SPACE OF THE WATER CLOSET.
  
 7F) THE TYPICAL ADA DOOR DETAIL SHOWS THE DOOR IN THE
 DOORWAY AND DIMENSIONED FROM JAMB TO JAMB 32 INCHES
 CLEAR. UNLESS THE DETAIL INDICATES THE USE OF OFFSET
 HINGES THAT THROUGH THE DOOR OUT OF THE JAMB, THE
 MINIMUM JAMB TO JAMB DIMENSION WOULD BE 2'-10" THAT
 WILL ALLOW 32 INCHES OF CLEAR OPENING.
 2010 FL ACESS. CODE 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  