Plan Review Notes
Plan Review Notes For Permit 14110596
Permit Number 14110596
Review Stop B
Sequence Number 3
Notes
Date Text
2015-01-27 16:36:29PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT
 CLEAR AND APPEARS TO BE INCORRECT.
 A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF
 AREAS APPEAR TO BE INCORRECT FOR A STRUCTURE LOCATED IN
 EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN
 ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE
 DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1
 AND ASCE 7-10 CHAPTER 30.
  
 B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE
 THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER
 ROOF AREAS. FBC 107.2.1.3
  
 C) FOR EACH OF THE THREE ROOF ZONES. SPECIFY THE
 FASTENER SPACING AT THE 3" LAP AND IN THE (TWO OR MORE
 IF REQUIRED) STAGGERED ROWS IN THE CENTER OF THE
 SHEETS.
  
 2) RAS 117 SECTION 8.1 STATES THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4 INCHES ON CENTER.
 THE DOCUMENT FROM JOHN D. BUEROSSE, P.E. STATES THAT
 THE LAPS SHOULD BE NAILED AT 3" APART IN ZONE 3