Plan Review Notes For Permit 14110596 |
Permit Number |
14110596 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-16 09:00:04 | PLAN REVIEW COMMENTS | | | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT | | CLEAR AND APPEARS TO BE INCORRECT. | | A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF | | AREAS APPPEAR TO BE TOO LOW FOR A STRUCTURE LOCATED IN | | EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN | | ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE | | DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1 | | AND ASCE 7-10 CHAPTER 30. | | | | B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE | | THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER | | ROOF AREAS. FBC 107.2.1.3 | | | | C) FOR EACH OF THE THREE ROOF ZONES. SPECIFY THE | | FASTENER SPACING AT THE 3" LAP AND IN THE TWO STAGGERED | | ROWS IN THE CENTER OF THE SHEETS. THE FASTENER SPACING | | THAT IS SPECIFIED IN THE NOA IS SUFFICIENT FOR THE | | FIELD ROOF AREA (ROOF ZONE 1). | | |
|