 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT
 CLEAR AND APPEARS TO BE INCORRECT.
 A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF
 AREAS APPPEAR TO BE TOO LOW FOR A STRUCTURE LOCATED IN
 EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN
 ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE
 DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1
 AND ASCE 7-10 CHAPTER 30.
  
 B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE
 THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER
 ROOF AREAS. FBC 107.2.1.3
  
 C) FOR EACH OF THE THREE ROOF ZONES. SPECIFY THE
 FASTENER SPACING AT THE 3" LAP AND IN THE TWO STAGGERED
 ROWS IN THE CENTER OF THE SHEETS. THE FASTENER SPACING
 THAT IS SPECIFIED IN THE NOA IS SUFFICIENT FOR THE
 FIELD ROOF AREA (ROOF ZONE 1).
  