2014-11-19 10:45:02PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE RAS 117 INFORMATION THAT WAS SUBMITTED IS NOT
 CLEAR AND APPEARS TO BE INCORRECT.
 A) THE COMPONENT AND CLADDING PRESSURES FOR THE ROOF
 AREAS APPPEAR TO BE TOO LOW FOR A STRUCTURE LOCATED IN
 EXPOSURE C WITH 170 MPH VULT. WIND SPEED AND A 24' MEAN
 ROOF HEIGHT. SPECIFY HOW THESE PRESSURES WERE
 DETERMINED. PROVIDE ALL CALCULATIONS. FBC - R301.2.1
 AND ASCE 7-10 CHAPTER 30.
  
 B) PROVIDE THE CALCULATIONS THAT WERE USED TO DETERMINE
 THE ENHANCED FASTENING FOR THE PERIMETER AND CORNER
 ROOF AREAS. FBC 107.2.1.3
  
 C) SPECIFY THE DIMENSIONS OF THE PERIMETER AND CORNER
 ROOF AREAS. SHOW THE CALCULATIONS THAT WERE USED TO
 DETERMINE THEM. FBC 107.2.1.3
  
 2) THE VALUE FOR THE WORK OF $11,500.00 IS LOW AND HAS
 BEEN INCREASED TO $15,900.00 BASED ON MARSHALL & SWIFT
 VALUATION. FBC 109.3
  