2014-11-20 09:50:11 | 1) THE WORK ORDER FROM DIG IT SHOWS A BBQ GRILL GAS |
| LINE TO BE INSTALLED BUT THE OUTLET IS NOT SHOWN ON THE |
| GAS RISER. THE CONNECTION TO THE POOL HEATER IS NOT |
| SHOWN ON THE WORK ORDER EITHER. CLARIFY. SHOW ALL |
| APPLIANCES ON THE GAS RISER.WPB AMEND. TO 2010 FBC SEC. |
| 107.2.1. |
| 2) SHOW THE DISTANCE OF THE LP TANK FROM THE EDGE OF |
| THE DRIVEWAY ON THE COPY OF THE SURVEY.COMPLY WITH NFPA |
| 58 SEC.6.6.6.1 (D). |
| 3) SHOW THE LOCATION OF THE REGULATORS AND REQUIRED |
| SHUTOFF VALVES ON THE GAS RISER. WPB AMEND. TO 2010 FBC |
| SEC. 107.2.1. |
| 4) THE GAS RISER SHOWS THE GAS PIPE CONTINUING TO |
| NOWHERE AFTER THE TEE TO THE RANGE. CLARIFY. SHOW THE |
| LENGTH OF THIS SECTION OF PIPE AND IT'S TERMINATION |
| POINT. |
| 5) SPECIFICATIONS FROM 2 DIFFERENT TANK MANUFACTURERS |
| HAVE BEEN SUBMITTED; ONE FROM AMERICAN WELDING & ONE |
| FROM TRINITY CONTAINERS. CLARIFY. |
| 6) THE SHEET FROM AMERICAN WELDING IS ILLEGIBLE. SUBMIT |
| A CLEAR AND LEGIBLE COPY.WPB AMEND. TO 2010 FBC SEC. |
| 107.2.1. |
| 7) SEVERAL SPECS HAVE BEEN SUBMITTED FROM UNKNOWN |
| SOURCES (SIDE MOUNT TANK ANCHORING AND AN UNDERGROUND |
| INSTALLATION DETAIL. WHERE DO THESE DETAILS COME FROM? |
| WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 8) SUBMIT LEGIBLE SHEETS FOR THE CATHODIC PROTECTION |
| INFORMATION FROM MESA. WPB AMEND. TO 2010 FBC SEC. |
| 107.2.1 |
| 9) INDICATE ON THE GAS RISER THE LENGTH OF SECTION OF |
| PIPE FROM THE TEE IN THE 3/4" PE LINE TO THE POOL |
| HEATER.AND FROM THE TEE IN THE PE LINE TO THE TEE FOR |
| THE RANGE. |
| 10) IT APPEARS THAT THE LONGEST RUN IS MORE THAN 170 |
| FT. THERE ARE SECTIONS OF PIPING WITH NO LENGTHS |
| SHOWN.CLARIFY. |
| 11) GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE |
| 2010 FGC SEC.301.3. |
| |