2015-05-15 08:29:13 
 2ND REVIEW: FBC 2010 MECHANICAL
 CHRISTOPHER COLE
  
 1) THE SUBMITTED AC PLAN NEEDS TO BE BE ENLARGED FOR
 CLARITY: THE NOTES AND DETAILS ARE NOT LEGIBLE- SECTION
 106.1.1 WPB AMENDMENTS TO THE FBC-10 BUILDING CODE.
 2) 2ND REQUEST FOR NEW RESTROOM EXHAUST DETAILS:
 EQUIPMENT SCHEDULE FOR FAN, EXHAUST DUCT SPECS, DUCT
 RUN AND TERMINATION LOCATION.
 3) 2ND REQUEST FOR ENERGY CALCULATIONS FOR THE TWO NEW
 TENANT SPACES- SEE SECTION 701.3 AND 711.1 FBC-10
 EXISTING BUILDING CODE; AND TABLE 101.4.1 FBC-10 ENERGY
 CONSERVATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER