2014-12-18 16:41:25 | 12/18/2014 |
| PROJECT: INTERIOR |
| PERMIT#: 14110576 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE ADDITIONA INFORMATION TO CLARIFY NEW PANEL |
| "B" ON THE "EXISTING FLOOR PLAN THERE IS NO PANEL "B" |
| IN THE PROPOSED FLOOR PLAN THERE IS A PANEL "B" ON THE |
| NEW RESTROOM PARTITION. THERE IS A RISER DIAGRAM SHOWN |
| ON THE SAME PAGE BUT IT IS SHOWN AS EXISTING. PLEASE |
| REVISE PLANS FOR CLARIFICATION. |
| |
| 2) CLARIFY THE PURPOSE OF THE RECEPTACLE SYMBOL ABOOVE |
| THE DOORS BY THE EXIT LIGHTS. |
| |
| 3) MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION |
| 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE |
| A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE |
| INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL |
| NOT BE REDUCED. FBC 713.3.2 MEMBRANE PENETRATIONS. |
| REVISE THE PLANS FOR COMPLIANCE. |
| |
| 4) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| |
| 5) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT |
| SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. |
| NEC 700.12 |
| |
| 6) REVISE THE FLOOR PLAN TO INDICATE ALL CIRCUIT |
| NUMBERS AS THEY COINCIDE TO THE CIRCUIT DIRECTORY(S). |
| |
| 7) ALL NEW RECEPTACLE OUTLETS SHALL BE TAMPER |
| SESISTANT. NEC 406.11 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |