Date Text
2014-12-18 16:41:2512/18/2014
 PROJECT: INTERIOR
 PERMIT#: 14110576
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ADDITIONA INFORMATION TO CLARIFY NEW PANEL
 "B" ON THE "EXISTING FLOOR PLAN THERE IS NO PANEL "B"
 IN THE PROPOSED FLOOR PLAN THERE IS A PANEL "B" ON THE
 NEW RESTROOM PARTITION. THERE IS A RISER DIAGRAM SHOWN
 ON THE SAME PAGE BUT IT IS SHOWN AS EXISTING. PLEASE
 REVISE PLANS FOR CLARIFICATION.
  
 2) CLARIFY THE PURPOSE OF THE RECEPTACLE SYMBOL ABOOVE
 THE DOORS BY THE EXIT LIGHTS.
  
 3) MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION
 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE
 A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. FBC 713.3.2 MEMBRANE PENETRATIONS.
 REVISE THE PLANS FOR COMPLIANCE.
  
 4) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 5) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 NEC 700.12
  
 6) REVISE THE FLOOR PLAN TO INDICATE ALL CIRCUIT
 NUMBERS AS THEY COINCIDE TO THE CIRCUIT DIRECTORY(S).
  
 7) ALL NEW RECEPTACLE OUTLETS SHALL BE TAMPER
 SESISTANT. NEC 406.11
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  