2014-12-02 14:20:14 | BUILDING PLAN REVIEW |
| PERMIT: 14110576 |
| ADD: 6230 S DIXIE HWY, UNIT 6230A & 6230 B |
| CONT: CARLOS GONZALEX |
| TEL: (561)386-8217 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 02/ 2014 |
| ACTION: DENIED |
| |
| 1) SHEET 2 OF 3 INDICATES THE SPLITTING THE TENANTCY |
| INTO 2 SMALLER TENANT SPACES. THE TENANT WALL IS SHOWN |
| AS DETAIL A THIS SHEET. THE DETAIL INDICATES A 1 HOUR |
| FIRE RATED WALL WITH 3 5/8 IN. METAL STUDS CENTER TO |
| CENTER NOT GIVEN AND 5/8 IN DRYWALL. PLEASE PROVIDE THE |
| ASSEMBLY FROM UL OR THE GYPSUM ASSOCIATION WHERE 5/8 |
| INCH DRYWALL PROVIDES A ONE HOUR RATING. EVEN THE 2010 |
| FBC-B TABLE 720.1(2) (16) INDICATES THE USE OF 5/8 INCH |
| TYPE X DRYWALL FOR FIRE RATED WALLS. |
| |
| 2) THR NEW PROPOSED TENANT SEPARATION WALL DETAIL IS |
| NOT CLEAR WHERE THE TOP OFTHE WALL IS GOING TO STOP, |
| SHOW COMPLIANCE WITH SECTION 709.4 CONTINUITY. FIRE |
| PARTITIONS SHALL EXTEND FROM THE TOP OF THE FOUNDATION |
| OR FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE |
| FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE |
| FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO. |
| IF THE PARTITIONS ARE NOT CONTINUOUS TO THE SHEATHING, |
| DECK OR SLAB, AND WHERE CONSTRUCTED OF COMBUSTIBLE |
| CONSTRUCTION, THE SPACE BETWEEN THE CEILING AND THE |
| SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR |
| DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 717.2 AND |
| 717.3 AT THE PARTITION LINE. THE SUPPORTING |
| CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED |
| FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT |
| FOR WALLS SEPARATING TENANT SPACES IN COVERED MALL |
| BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS |
| SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN |
| BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION |
| |
| 3) THE EXISTING FRONT STOREFRONT PANEL IS BEING REMOVED |
| AND A ALCOVE IS BEING CREATED. THIS CONSTRUCTION IS TO |
| BE WEATHER TIGHT THERE IS NO WALL IDENTIFYING TAGS IN |
| THIS WALL SECTION, NOR IS THERE A SECTION THROUGH THE |
| CEILING AS TO THE MATERIALS TO CREATE THE ALCOVE |
| CEILING NOR THE FRAMING ABOVE. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION,107.2.1.3.ADDITIONAL |
| INFORMATION REQUIRED. NOTE THIS IS A EXTERIOR WALL AND |
| WILL HAVE TO MEET THE PRESSURES FOR 170 VULT WIND |
| LOADING, PARTOF THE MWFRS, MAIN WIND FORCE RESISTING |
| SYSTEM. |
| |
| 4) .2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| |
| 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| TUS.ASPX FOR PERMIT STATUS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |