Plan Review Notes For Permit 14110550 |
Permit Number |
14110550 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-11-25 13:20:34 | 1) SUBMIT A SITE PLAN SHOWING THE LOCATION AND SIZE OF | | THE EXISTING GREASE TRAP. WPB AMEND. TO 2010 FPC SEC. | | 107.2.1. | | 2) SUBMIT CALCULATIONS THAT CONFIRM THAT THE EXISTING | | GREASE TRAP HAS THE CAPACITY FOR THIS OPERATION. | | 3) THE WATER CLOSET IN THE WOMEN'S RESTROOM IS BEING | | WET VENTED AND A URINAL IS ON THE WET VENT WHICH IS IN | | VIOLATION OF THE 2010 FPC SEC.909.1. | | 4) SHT. A1.3 REFERS TO DETAL A/A3.1. THERE IS NO SHT. | | A3.1 IN THE PLANS. CLARIFY. | | 5) SHT. P0.2 - GAS DWG. - NOTES REFER TO GAS TABLE | | 402.4 (20). THIS TABLE IS FOR PE PIPE AND THERE IS NO | | PE PIPE SHOWN ON THE DRAWING. CLARIFY. |
|