2014-11-15 14:09:06 | BUILDING PLAN REVIEW |
| PERMIT: 14110550 |
| ADD: 1855 PALM BEACH LAKES SUITE # B-09 |
| CONT: FINE LINE CONSTRUCTION |
| TEL: (561)582-7880 X 306 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. NOV. 15/ 2014 |
| ACTION: DENIED |
| |
| NOTE: BEFORE PLAAN SUBMITTAL TO THE BUILDING |
| DEPARTMENT, THE PLANS ARE SUPPOSE TO HAVE THE STAMPED |
| LANDLORD APPROVAL BY NEW ENGLAND DEVELOPMNT PALM BEACH |
| OUTLETS SKE GROUP TENANT COORDINATOR. |
| |
| 1) THE COVERSHEET: |
| |
| 1A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| (3.) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). THE SHELL PERMIT FOR BUILDING B2 IS A |
| BUILDING TYPE IIB. |
| |
| 1B) THE CLASSIFICATION OF THIS WORK IS SHOWN AS UNDER |
| THE 2010 FL. EXST, BLDG CODE, AS A LEVEL II. PLEASE |
| NOTE THERE HAS ONLY BEEN PROVIDED A CERTIFICATE OF |
| COMPLETION UNDER THE SHELL PERMIT. THIS BEING THE FIRST |
| TENANCY OF THIS SPACE WILL RECEIVE A CERTIFICATE OF |
| OCCUPANCY AND UNDER THE |
| 2010 FBC-B FOR NEW BUILDINGS. |
| 111.4 CERTIFICATE OF COMPLETION. |
| |
| 2) PLEASE SEE SHEET S2.0 NOTE MEZZANINE FRAMING NOTE M3 |
| INDICATES THE USE OF 2 LAYERS OF 3/4 INCH TYPE X |
| PLYWOOD. PLEASE REVIEW FBC-B 603.1 ALLOWABLE MATERIALS. |
| COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| THROUGH 603.1.3. |
| |
| 3A) SHEET A1.0 & A2.0 NOTE # 28 BOTH SHEETS INDICATE |
| WOOD FRAME STAIRS, SEE STAIR DETAIL DRAWINGS. NONE |
| FOUND. SHEET S2.0 NOTE INDICATES THE STAIRS ARE TO BE |
| PRE-ENGINEERED WOOD STAIRS. NO DETAILS, NO DESIGN |
| CRITERIA PROVIDED FOR LIVE LOADS FBC-B TABLE 1607. |
| SHEET A1.3 SHOWS A PROPOSED DTAIL # 8/ A3.1, NO SUCH |
| SHEET IN PLANS. |
| |
| 1009.6 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL BE |
| BUILT OF MATERIALS CONSISTENT WITH THE TYPES PERMITTED |
| FOR THE TYPE OF CONSTRUCTION OF THE BUILDING, EXCEPT |
| THAT WOOD HANDRAILS SHALL BE PERMITTED FOR ALL TYPES OF |
| CONSTRUCTION. TYPE IIB CONSTRUCTION. |
| |
| 3B) THERE IS NO DESIGN INFORMATION AS WELL FOR THE |
| HANDRAIL SYSTEM AS REQUIRED BY FBC-B 1012. |
| |
| 3C) ARE THESE STAIRS GOING TO HAVE A CLOSED OR SOLID |
| RISER FBC-B 1009.4.5. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |