2014-11-13 17:36:44PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED
 BITUMEN ROOF SYSTEM NOA NO. 13-0416.05 HAS BEEN
 SUPERSEDED. SUBMIT TWO COPIES OF THE CURRENT NOA AS
 REQUIRED BY DCA RULE 9N-3.
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE THAT
 IS BEING RE-ROOFED. FBC-R 301.1
  
 3) SPECIFY THE APPROVED ASSEMBLY AND THE MAXIMUM DESIGN
 OF THE SYSTEM THAT WILL BE INSTALLED. THE STRUCTURE IS
 LOCATED IN EXPOSURE C WITH A 170 MPH WIND-SPEED. SUBMIT
 TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AT PERIMETER AND CORNER ROOF AREAS
 AS INDICATED IN LIMITATION NUMBER 7 ON PAGE 32 OF THE
 NOA. FBC-R 301.1