Plan Review Notes For Permit 14110508 |
Permit Number |
14110508 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-28 11:26:23 | SECOND REVIEW FBC 2010 | | | | THE COMMENTS FROM THE FIRST REVIEW WERE APPARENTLY NOT | | ADDRESSED. SEE BELOW. | | | | PLEASE PROVIDE A SYSTEM THAT CAPTURES THE CONTAMINANTS | | (PRODUCTS) AND ODORS AT THEIR SOURCE, MANICURE TABLES | | AS PER THE FLORIDA MECHANICAL CODE BELOW | | | | 403.3 OUTDOOR AIRFLOW RATE. | | TABLE 403.3?CONTINUED | | MINIMUM VENTILATION RATES | | | | | | H. FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE | | VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE | | CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE | | OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|