2014-11-25 11:37:10BUILDING PLAN REVIEW
 PERMIT: 14110470
 ADD: 4847 FRED GLADSTONE DRIVE
 CONT: THE WINDOW GUYS OF FLORIDA
 TEL: (561)598-6295
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 25/ 2014
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THIS IS UNDER A
 MASTER/ PRIME PERMIT. PERMIT # 12050519 IS A OPEN
 PERMIT THAT HAS NOT RECEIVED A CERTIFICATE OF
 OCCUPANCY, OR A CERTIFICATE OF COMPLETION. IN AS SUCH
 ANY CHANGES TO THE APPROVED PLANS WILL NEED TO BE
 REVIEWED BY THE DESIGNER OF RECORD. NOTE IF THE PERMIT
 SET OF ISSUED PLANS SHOWS A OPEN PORTE COCHERE, THEN
 THE DESIGNER OF RECORD WILL NEED TO SUBMIT A REVISION
 SHOWING THE ENCLOSING OF THIS SPACE. THE SPACE IS NO
 LONGER CONSIDERED A OPEN STRUCTURE IT WILL BE
 CONSIDERED ENCLOSED WITH NEW WIND LOADS AGAINST THE
 SIDES OF THE STRUCTURE, THE STRUCTURE WILL NEED TO BE
 EVALUATED BY THE DESIGN PROFESSIONALS FOR THE
 ADDITIONAL LOADS TO BE IMPOSED.
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; ALL FENESTRATION
 PENETRATIONS; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (1) SITE PLANS LOCATION OF STRUCTURE TO THE OVER ALL
 SITE
 (8) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS MISSING WIND DESIGN CRITERIA.
 BUILDING ENVELOPE
  
 2) TO BE REVIEWED BY THE DESIGNER OF RECORD BEFORE
 SUBMITTAL TO THE BUILDING DEPARTMENT. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC...
  
 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER
 ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECT?S
 OFFICE.
  
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9N-3 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) THE FLOOR PLANS SUBMITTED BY THE WINDOW GUY SHOWS
 WINDOW TYPE A & B TOTALLY SURROUNDING THE PORT COCHERE,
 HOW IS ENTRY TO BE GAINED THERE IS NO DOORWAY?
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  