Plan Review Notes
Plan Review Notes For Permit 14110465
Permit Number 14110465
Review Stop M
Sequence Number 1
Notes
Date Text
2014-11-17 13:15:13PLAN DENIED
 1) PROVIDE CAN SIZE AND GRILL SIZE ON PLANS
 2) PROVIDE CFM ON ALL SUPPLY DROPS
 3) PROVIDE EQUIPMENT SCHEDULE ON THE
 PLAN SHOWING MODEL NUMBERS,VOLTAGE
 AND SEER ALONG WITH AHRI SHEETS IF
 EQUIPMENT IS BEING REPLACED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  
  
  
  
2014-11-12 12:32:23COULD NOT DELETE ACTIVITY (PLACED MY NAME AS REVIEWER
 IN ERROR) SEE NEW "M" STOP