2014-12-19 09:53:14 | 12/19/2014 |
| PROJECT: PEARL PLACE |
| PERMIT#: 14110431 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) FL SS 471, 668.001-668.006, FBC, WPB AMENDMENTS |
| 107.2.1 |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 2) FBC-WPB AMENDMENTS 107.3.5.1.2 |
| NO ELECTRICAL PLANS HAVE BEEN SUBMITTED. THE MINIMUM |
| PLAN REVIEW CRITERIA FOR ELECTRICAL INCLUDES THE |
| FOLLOWING: |
| A.) AN ELECTRICAL SERVICE RISER, AND LOAD CALCULATION. |
| NEC 215.5 |
| B.) THE ELECTRICAL PANEL CIRCUIT DIRECTORIES, NEC 408.4 |
| C.) A FLOOR PLAN WITH CIRCUIT NUMBERS TO COINCIDE WITH |
| THE PANEL CIRCUIT DIRECTORY. FBC-WPB AMENDMENTS 107.3.5 |
| D.) A LIGHTING FIXTURE SCHEDULE AND LIGHTING PLAN, |
| FBC-WPB AMENDMENTS 107.3.5 |
| E.) THE EXIT AND EMERGENCY LIGHTING PLAN PROVIDING AN |
| ILLUMINATED MEANS OF EGRESS. NEC700.12 |
| F.) A SIGN CIRCUIT. NEC 600.5 |
| G.) WIRING METHODS SUITABLE FOR THE ENVIRONMENT. |
| ASSEMBLY OCCUPANCY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |