Plan Review Notes
Plan Review Notes For Permit 14110428
Permit Number 14110428
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-09 17:44:00RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND PROFESSIONAL DESIGN FEES. VALUATION WAS
 UPDATED TO $26,058. THE PERMIT FEE BALANCE IS $637.02.
  
 3- CLEARLY SPECIFY ON PLANS THE NAME OF THE ALTERED
 ROOM ADJACENT TO THE NEW BEDROOM ADDITION AS REQUIRED
 BY SEC. 401.3 OF 2010 FBC-EXISTING BUILDING. ROOM IS
 NOT DEFINED AND NEED TO VERIFY EGRESS REQUIREMENTS.
  
 4- WALL SECTION PROVIDED:
 A) LETTERING IS TOO SMALL AND IS MISSING INFORMATION.
 DRAWING WAS COPIED AND PASTED AND IS MISSING ALL THE
 INFORMATION ON THE LEFT HAND SIDE. REVISE AS REQUIRED.
 SEC. 107.2.1.4 CITY AMENDMENTS TO FBC.
  
 B) FOOTING INFORMATION IS NOT CLEAR. THERE IS
 INFORMATION REGARDING A STEM WALL, BUT THERE IS NOT
 STEM WALL SHOWN. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) CLEARLY SHOW THE FOOTING DIMENSION BELOW GRADE AND
 ABOVE GRADE. DIMENSION SHOWN IS OFFSET. COORDINATE WITH
 SIZE OF FOOTING SPECIFIED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC.
 R315 OF 2010 FBC-RESIDENTIAL.
  
 6- GABLE END BRACING DETAIL: PROVIDE COMPLETE
 SPECIFICATIONS FOR THE RAKE BEAM. THERE IS NOT BEAM
 SCHEDULE PROVIDED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) POLYGLASS ROOFING UNDERLAYMENT. NOA 11-1229.01
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE
 CURRENT NOA.
  
 B) FIXED WINDOWS: NEED PRODUCT APPROVAL THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ARCHITECT. NOA
 11-1114.14 SUBMITTED DOESN'T MEET CALCULATED DESIGN
 PRESSURES.
  
 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- DESIGN PRESSURES CALCULATED BY THE ARCHITECT FOR THE
 NEW 72" X 60" STOREFRONT FIXED WINDOWS ARE TOO LOW.
 REVISE AS REQUIRED. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 10- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE ITEM #12B: NEED 13 SEER MIN.. SEE GENERAL
 INSTRUCTION NOTE #2 OF ENERGY CALCULATIONS SUBMITTED.
  
 (NOTE: HOUSE IS A HISTORIC CONTRIBUTING HOUSE. ENERGY
 CALCULATIONS ARE NOT REQUIRED).
  
 11- ARCHITECT TO PROVIDE DETAIL AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE R7.8 INSULATION ON MASONRY
 WALLS AS REQUIRED BY THE ENERGY CALCULATIONS SUBMITTED.
  
 12- PROVIDE WINDOWS AND DOORS MANUFACTURER'S SPECS
 SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON ITEM #6 OF ENERGY CALCULATIONS SUBMITTED.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 13- SOIL TEST REPORT NEEDS ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  
 13- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF STORM SHUTTERS. YOU CAN USE THE CITY
 SAMPLE FOR STORM SHUTTERS INSTALLATION SCHEDULE OR USE
 ANY OTHER FORMAT THAT PROVIDES ALL THE REQUIRED
 INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
  