Plan Review Notes
Plan Review Notes For Permit 14110421
Permit Number 14110421
Review Stop P
Sequence Number 2
Notes
Date Text
2015-01-04 07:37:201) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED PER
 THE FL. ACCESSIBILITY CODE SEC. 211.2. SINCE THIS IS A
 CHANGE OF OCCUPANCY FULL COMPLIANCE WITH THE FL.
 ACCESSIBILITY CODE IS REQUIRED.
 2) A MINIMUM OF ONE SINK IN EACH OF THE 2 YEAR OLD'S
 ROOMS SHALL COMPLY WITH THE FL. ACCESSIBILITY CODE
 SECS. 212.2, AND 606. SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE FIXZTURE ON THE FLOOR PLAN.
 3) SUBMIT A SANITARY AND WATER RISER FOR THE
 ADDITIONS/ALTERATIONS THAT ARE GOING TO BE MADE TO THE
 PLUMBING SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1.